Assessment Year | 1997 |
---|---|
Principal Product | Surfactants |
NAICS |
n/a
|
SIC | 2843: Surface Active Agents, Finishing Agents, Sulfonated Oils, and Assistants |
Sales Range | $10 M to 50M |
# of Employees | 100 |
Plant Area |
180,000
ft2
|
Annual Production | 100,000,000
lb
|
Production Hrs. Annual | 8,400
hrs
|
Location (State) | South Carolina |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $218,603 | 7,400,352 |
kWh
|
$0.030 |
Electricity Demand | $112,990 | 11,794 |
kW-mo/yr
|
$9.58 |
Electricity Fees | $37,377 | - |
|
- |
Natural Gas | $396,631 | 118,820 |
MMBtu
|
$3.34 |
Fuel Oil #2 | $12,884 | 2,843 |
MMBtu
|
$4.53 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $303,909 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $9,105 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings | Natural Gas Savings | Water Disposal Savings | Increase in Production Savings |
---|---|---|---|---|---|---|---|---|---|---|
01 | 2.8112: Combine utility meters | $78,900 | - | - | - | $78,900 | - | - | - | |
02 | 2.2414: Use waste heat from hot flue gases to preheat | $22,270 | $19,740 | - | - | - |
$22,270
-
MMBtu
|
- | - | |
03 | 2.1241: Reduce excessive boiler blowdown | $3,060 | - | - | - | - |
$3,060
-
MMBtu
|
- | - | |
04 | 4.652: Replace existing equipment with more suitable substitutes | $181,260 | $181,000 | - | - | - |
$6,260
-
MMBtu
|
- | $175,000 | |
05 | 3.4111: Use closed cycle process to minimize waste water production | $9,314 | $12,000 | - | - | - |
$7,425
-
MMBtu
|
$1,889
-
Tgal
|
- | |
06 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $3,245 | $4,110 |
$2,142
72,392
kWh
|
$1,103
-
kW-mo/yr
|
- | - | - | - | |
07 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $5,860 | $11,000 |
$4,216
142,732
kWh
|
$1,218
-
kW-mo/yr
|
$426 | - | - | - | |
TOTAL RECOMMENDED | $303,909 | $227,850 |
$6,358
215,124
kWh
|
$2,321
-
kW-mo/yr
|
$79,326 |
$39,015
-
MMBtu
|
$1,889
-
Tgal
|
$175,000 | ||
TOTAL IMPLEMENTED | $9,105 | $15,110 |
$6,358
215,124
kWh
|
$2,321
-
kW-mo/yr
|
$426 | - | - | - | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings | Natural Gas Savings | Water Disposal Savings | Increase in Production Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs