Assessment Year | 1993 |
---|---|
Principal Product | Cotton Cloth |
NAICS |
n/a
|
SIC | 2211: Broadwoven Fabric Mills, Cotton |
Sales Range | $10 M to 50M |
# of Employees | 500 |
Plant Area |
n/a
|
Annual Production | 53,300,000
thousand feet
|
Production Hrs. Annual | 8,400
hrs
|
Location (State) | South Carolina |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $1,219,129 | 33,518,465 |
kWh
|
$0.036 |
Natural Gas | $81,022 | 31,697 |
MMBtu
|
$2.56 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $117,235 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $112,515 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Natural Gas Savings |
---|---|---|---|---|---|---|
01 | 2.7122: Disconnect ballasts | $6,945 | $9,090 |
$6,945
190,797
kWh
|
- | |
02 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $22,915 | $63,140 |
$22,915
629,836
kWh
|
- | |
03 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $80 | $955 |
$80
2,345
kWh
|
- | |
04 | 2.7135: Install occupancy sensors | $2,400 | $500 |
$2,400
65,944
kWh
|
- | |
05 | 2.4146: Use adjustable frequency drive or multiple speed motors on existing system | $73,000 | $116,200 |
$73,000
2,006,155
kWh
|
- | |
06 | 2.4111: Utilize energy-efficient belts and other improved mechanisms | $9,655 | $37,220 |
$9,655
265,240
kWh
|
- | |
07 | 2.1221: Replace obsolete burners with more efficient ones | $2,240 | $6,000 | - |
$2,240
-
MMBtu
|
|
TOTAL RECOMMENDED | $117,235 | $233,105 |
$114,995
3,160,317
kWh
|
$2,240
-
MMBtu
|
||
TOTAL IMPLEMENTED | $112,515 | $225,650 |
$112,515
3,092,028
kWh
|
- | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Natural Gas Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs