Assessment Year 1992
Principal Product UNIFORMS
NAICS
n/a
SIC 2329: Men's and Boys' Clothing, Not Elsewhere Classified
Sales Range $10
M
to 50
M
# of Employees 280
Plant Area
n/a
Annual Production 700,000
pieces
Production Hrs. Annual 2,700
hrs
Location (State) Alabama

Facility Energy Cost and Usage

Source Yearly Cost Usage
Electricity Usage $58,644 703,693
kWh
Natural Gas $3,268 617
MMBtu
LPG $8,769 801
MMBtu
TOTAL YEARLY COSTS -
RECOMMENDED SAVINGS* $15,981 *Non-energy impacts included in savings.
IMPLEMENTED SAVINGS* $15,981

Recommendations

# Description Yearly Savings* Imp'd Cost* Status Electricity Usage Savings Natural Gas Savings LPG Savings Administrative Changes Savings
01 2.7142: Utilize higher efficiency lamps and/or ballasts $3,463 $20,590 $3,849
49,238
kWh
- - $(-386.0)
02 2.7142: Utilize higher efficiency lamps and/or ballasts $180 $215 $180
2,345
kWh
- - -
03 2.4133: Use most efficient type of electric motors $117 $1,780 $117
1,172
kWh
- - -
04 2.3136: Overlap custodial services with normal day hours $3,837 - $3,837
48,945
kWh
- - -
05 2.7228: Avoid introducing hot, humid, or dirty air into hvac system $950 $460 $950
10,258
kWh
- - -
06 2.8114: Change rate schedules or other changes in utility service $2,908 $4,450 $2,908
-
kWh
- - -
07 2.1332: Convert combustion equipment to burn natural gas $4,526 $3,940 - $(-4,245.0)
-
MMBtu
$8,771
-
MMBtu
-
TOTAL RECOMMENDED $15,981 $31,435 $11,841
111,958
kWh
$(-4,245.0)
-
MMBtu
$8,771
-
MMBtu
$(-386.0)
TOTAL IMPLEMENTED $15,981 $31,435 $11,841
111,958
kWh
$(-4,245.0)
-
MMBtu
$8,771
-
MMBtu
$(-386.0)
Yearly Savings* Imp'd Cost* Electricity Usage Savings Natural Gas Savings LPG Savings Administrative Changes Savings
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs