Assessment Year | 1987 |
---|---|
Principal Product | MARGARINE |
NAICS |
n/a
|
SIC | 2079: Shortening, Table Oils, Margarine, and Other Edible Fats and Oils, Not Elsewhere Classified |
Sales Range | $50 M to 100M |
# of Employees | 225 |
Plant Area |
n/a
|
Annual Production | 161,000
lb
|
Production Hrs. Annual | 4,800
hrs
|
Location (State) | Alabama |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $406,931 | 5,815,944 |
kWh
|
$0.070 |
Natural Gas | $94,573 | 19,485 |
MMBtu
|
$4.85 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $56,843 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $48,480 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Natural Gas Savings | Administrative Changes Savings |
---|---|---|---|---|---|---|---|
01 | 2.1233: Analyze flue gas for proper air/fuel ratio | $2,910 | $300 | - |
$2,910
-
MMBtu
|
- | |
02 | 2.2163: Use minimum steam operating pressure | $850 | - | - |
$850
-
MMBtu
|
- | |
03 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $1,990 | $2,430 |
$1,990
28,722
kWh
|
- | - | |
04 | 2.2121: Increase amount of condensate returned | $8,110 | $4,400 | - |
$4,610
-
MMBtu
|
$3,500 | |
05 | 2.4111: Utilize energy-efficient belts and other improved mechanisms | $13,200 | $12,400 |
$13,200
189,039
kWh
|
- | - | |
06 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $19,500 | $39,600 |
$19,500
276,084
kWh
|
- | - | |
07 | 2.4133: Use most efficient type of electric motors | $2,483 | $3,725 |
$2,483
35,463
kWh
|
- | - | |
08 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $2,770 | $8,290 |
$2,770
39,566
kWh
|
- | - | |
09 | 2.2414: Use waste heat from hot flue gases to preheat | $5,030 | $15,000 | - |
$5,030
-
MMBtu
|
- | |
TOTAL RECOMMENDED | $56,843 | $86,145 |
$39,943
568,874
kWh
|
$13,400
-
MMBtu
|
$3,500 | ||
TOTAL IMPLEMENTED | $48,480 | $67,420 |
$37,460
533,411
kWh
|
$7,520
-
MMBtu
|
$3,500 | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Natural Gas Savings | Administrative Changes Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs