| Assessment Year | 1983 |
|---|---|
| Principal Product | CARPET |
| NAICS |
n/a
|
| SIC | 2273: Carpets and Rugs |
| Sales Range | $50 M to 100M |
| # of Employees | 300 |
| Plant Area |
n/a
|
| Annual Production | 28,800
thousand feet
|
| Production Hrs. Annual | 6,000
hrs
|
| Location (State) | Georgia |
Facility Energy Cost and Usage
| Source | Yearly Cost | Usage | Unit Cost | |
|---|---|---|---|---|
| Electricity Usage | $243,042 | 4,116,940 |
kWh
|
$0.059 |
| Natural Gas | $885,248 | 192,912 |
MMBtu
|
$4.59 |
| TOTAL YEARLY COSTS | - | |||
| RECOMMENDED SAVINGS* | $240,455 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
| IMPLEMENTED SAVINGS* | $240,455 | |||
Recommendations
| # | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Natural Gas Savings |
|---|---|---|---|---|---|---|
| 01 | 2.1233: Analyze flue gas for proper air/fuel ratio | $15,132 | $500 | - |
$15,132
-
MMBtu
|
|
| 02 | 2.2414: Use waste heat from hot flue gases to preheat | $28,745 | $50,000 | - |
$28,745
-
MMBtu
|
|
| 03 | 2.1243: Use heat from boiler blowdown to preheat boiler feed water | $22,837 | $10,000 | - |
$22,837
-
MMBtu
|
|
| 04 | 2.5191: Modify dye beck | $58,597 | $101,000 | - |
$58,597
-
MMBtu
|
|
| 05 | 2.5191: Modify dye beck | $38,740 | $51,000 | - |
$38,740
-
MMBtu
|
|
| 06 | 2.5192: Modify textile dryers | $33,809 | $35,000 | - |
$33,809
-
MMBtu
|
|
| 07 | 2.1111: Control pressure on steamer operations | $7,770 | $3,500 | - |
$7,770
-
MMBtu
|
|
| 08 | 2.2135: Repair and eliminate steam leaks | $4,897 | $400 | - |
$4,897
-
MMBtu
|
|
| 09 | 2.7492: Use proper thickness of insulation on building envelope | $2,028 | $4,000 |
$1,059
20,223
kWh
|
$969
-
MMBtu
|
|
| 10 | 2.3191: Use demand controller or load shedder | $27,900 | $50,000 |
$27,900
-
kWh
|
- | |
| TOTAL RECOMMENDED | $240,455 | $305,400 |
$28,959
20,223
kWh
|
$211,496
-
MMBtu
|
||
| TOTAL IMPLEMENTED | $240,455 | $305,400 |
$28,959
20,223
kWh
|
$211,496
-
MMBtu
|
||
| Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Natural Gas Savings | |||
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs