| Assessment Year | 1995 |
|---|---|
| Principal Product | Granite monuments and tiles |
| NAICS |
n/a
|
| SIC | 3281: Cut Stone and Stone Products |
| Sales Range | $5 M to 10M |
| # of Employees | 70 |
| Plant Area |
110,700
ft2
|
| Annual Production | 345,000
pieces
|
| Production Hrs. Annual | 2,280
hrs
|
| Location (State) | South Dakota |
Facility Energy Cost and Usage
| Source | Yearly Cost | Usage | Unit Cost | |
|---|---|---|---|---|
| Electricity Usage | $232,456 | 4,361,372 |
kWh
|
$0.053 |
| Natural Gas | $4,348 | 790 |
MMBtu
|
$5.50 |
| Fuel Oil #1 | $11,921 | 2,556 |
MMBtu
|
$4.66 |
| TOTAL YEARLY COSTS | - | |||
| RECOMMENDED SAVINGS* | $29,294 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
| IMPLEMENTED SAVINGS* | $25,037 | |||
Recommendations
| # | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Natural Gas Savings |
|---|---|---|---|---|---|---|
| 01 | 2.4133: Use most efficient type of electric motors | $6,723 | $28,139 |
$6,723
96,424
kWh
|
- | |
| 02 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $5,231 | $200 |
$5,231
154,455
kWh
|
- | |
| 03 | 2.7231: Use radiant heater for spot heating | $13,083 | $12,000 |
$28,844
712,485
kWh
|
$(-15,761.0)
-
MMBtu
|
|
| 04 | 2.4321: Upgrade obsolete equipment | $4,257 | $950 |
$4,257
75,615
kWh
|
- | |
| TOTAL RECOMMENDED | $29,294 | $41,289 |
$45,055
1,038,979
kWh
|
$(-15,761.0)
-
MMBtu
|
||
| TOTAL IMPLEMENTED | $25,037 | $40,339 |
$40,798
963,364
kWh
|
$(-15,761.0)
-
MMBtu
|
||
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs