| Assessment Year | 2025 |
|---|---|
| Principal Product | Plastic Parts for Boating Industry |
| NAICS | 336612: Boat Building |
| SIC | 3089: Plastics Products, Not Elsewhere Classified |
| Sales Range | $1 M to 5M |
| # of Employees | 15 |
| Plant Area |
23,000
ft2
|
| Annual Production | 100,000
units
|
| Production Hrs. Annual | 2,750
hrs
|
| Location (State) | Delaware |
Facility Energy Cost and Usage
| Source | Yearly Cost | Usage | Unit Cost | |
|---|---|---|---|---|
| Electricity Usage | $21,307 | 175,436 |
kWh
|
$0.12 |
| Electricity Demand | $5,130 | 368 |
kW-mo/yr
|
$13.94 |
| Electricity Fees | $1,080 | - |
|
- |
| LPG | $10,080 | 320 |
MMBtu
|
$31.50 |
| TOTAL YEARLY COSTS | $37,597 | |||
| RECOMMENDED SAVINGS* | $13,212 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
| IMPLEMENTED SAVINGS* | - | |||
Recommendations
| # | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | LPG Savings |
|---|---|---|---|---|---|---|---|
| 01 | 2.7224: Reduce space conditioning during non-working hours | $1,316 | - |
$1,055
8,717
kWh
|
$261
-
kW-mo/yr
|
- | |
| 02 | 2.2449: Recover heat from exhausted steam, hot air or hot water | $1,212 | $2,300 | - | - |
$1,212
-
MMBtu
|
|
| 03 | 2.4146: Use adjustable frequency drive or multiple speed motors on existing system | $689 | $1,400 |
$552
4,565
kWh
|
$137
-
kW-mo/yr
|
- | |
| 04 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $317 | $500 |
$254
2,098
kWh
|
$63
-
kW-mo/yr
|
- | |
| 05 | 2.4146: Use adjustable frequency drive or multiple speed motors on existing system | $2,109 | $9,700 |
$1,690
13,967
kWh
|
$419
-
kW-mo/yr
|
- | |
| 06 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $2,511 | $2,607 |
$2,013
16,632
kWh
|
$499
-
kW-mo/yr
|
- | |
| 07 | 2.7243: Improve air circulation with destratification fans / other methods | $988 | $5,100 | - | - |
$988
-
MMBtu
|
|
| 08 | 2.7492: Use proper thickness of insulation on building envelope | $1,533 | $7,200 | - | - |
$1,533
-
MMBtu
|
|
| 09 | 2.7292: Lower ceiling to reduce conditioned space | $2,537 | $20,700 |
$(-389.0)
(-3,215)
kWh
|
$(-96.0)
-
kW-mo/yr
|
$3,022
-
MMBtu
|
|
| TOTAL RECOMMENDED | $13,212 | $49,507 |
$5,174
42,764
kWh
|
$1,283
-
kW-mo/yr
|
$6,755
-
MMBtu
|
||
| TOTAL IMPLEMENTED | - | - | - | - | - | ||
| Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | LPG Savings | |||
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs