Assessment Year | 2022 |
---|---|
Principal Product | Paper-backed foam sheets and rolls |
NAICS | 326113: Unlaminated Plastics Film and Sheet (except Packaging) Manufacturing |
SIC | 3081: Unsupported Plastics Film and Sheet |
Sales Range | $10 M to 50M |
# of Employees | 149 |
Plant Area |
100,000
ft2
|
Annual Production | 25,900
thousand feet
|
Production Hrs. Annual | 8,568
hrs
|
Location (State) | Delaware |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $94,840 | 2,063,711 |
kWh
|
$0.046 |
Electricity Demand | $45,258 | 4,092 |
kW-mo/yr
|
$11.06 |
Electricity Fees | $7,898 | - |
|
- |
Natural Gas | $55,837 | 6,144 |
MMBtu
|
$9.09 |
TOTAL YEARLY COSTS | $203,833 | |||
RECOMMENDED SAVINGS* | $75,273 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | - |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings |
---|---|---|---|---|---|---|---|
01 | 2.1132: Repair faulty louvers and dampers | $20,616 | $975 | - | - |
$20,616
-
MMBtu
|
|
02 | 2.4322: Use or replace with energy efficient substitutes | $4,912 | $5,000 |
$3,323
72,241
kWh
|
$1,589
-
kW-mo/yr
|
- | |
03 | 2.7224: Reduce space conditioning during non-working hours | $634 | $495 |
$73
1,575
kWh
|
$35
-
kW-mo/yr
|
$527
-
MMBtu
|
|
04 | 2.2437: Recover waste heat from equipment | $5,199 | $6,100 | - | - |
$5,199
-
MMBtu
|
|
05 | 2.2443: Re-use or recycle hot or cold process exhaust air | $3,655 | $5,200 | - | - |
$3,655
-
MMBtu
|
|
06 | 2.2515: Use optimum thickness insulation | $692 | $2,233 | - | - |
$692
-
MMBtu
|
|
07 | 2.2622: Replace existing chiller with high efficiency model | $11,396 | $21,500 |
$7,709
167,584
kWh
|
$3,687
-
kW-mo/yr
|
- | |
08 | 2.4146: Use adjustable frequency drive or multiple speed motors on existing system | $7,587 | $13,450 |
$5,133
111,580
kWh
|
$2,454
-
kW-mo/yr
|
- | |
09 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $278 | $210 |
$189
4,094
kWh
|
$89
-
kW-mo/yr
|
- | |
10 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $20,304 | $22,424 |
$13,735
298,585
kWh
|
$6,569
-
kW-mo/yr
|
- | |
TOTAL RECOMMENDED | $75,273 | $77,587 |
$30,162
655,659
kWh
|
$14,423
-
kW-mo/yr
|
$30,689
-
MMBtu
|
||
TOTAL IMPLEMENTED | - | - | - | - | - | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs