ITAC Assessment: OR0415
ITAC logo
ITAC Assessment: OR0415
Grant Funding Opportunity NOW OPEN
Up to $300k at 50% cost share for qualifying* projects.
Grant Funding Opportunity Open
Qualifying* small and medium-sized US manufacturers, that received an ITAC, Onsite Energy/CHP TAP, or qualified equivalent assessment since 2018 can now apply for grants for implementation of assessment recommendations at up to 50% of qualifying* project costs with a maximum of $300,000 per grant.
IMPORTANT: The grant program now operates on a rolling basis and applications may be submitted at any time through the year, with quarterly reviews.
*See Full Grant Solicitation for full qualification and selection details.
Assessment Year 2002
Principal Product Plastics
NAICS
n/a
SIC 3089: Plastics Products, Not Elsewhere Classified
Sales Range $10
M
to 50
M
# of Employees 131
Plant Area
n/a
Annual Production 169
ton
Production Hrs. Annual 3,000
hrs
Location (State) Washington

Facility Energy Cost and Usage

Source Yearly Cost Usage
Electricity Usage $170,029 2,905,101
kWh
Electricity Demand $13,403 13,008
kW-mo/yr
Electricity Fees $1,434 -
Natural Gas $33,317 4,915
MMBtu
TOTAL YEARLY COSTS -
RECOMMENDED SAVINGS* $48,409 *Non-energy impacts included in savings.
IMPLEMENTED SAVINGS* -

Recommendations

# Description Yearly Savings* Imp'd Cost* Status Electricity Usage Savings Electricity Demand Savings Electricity Fees Savings Natural Gas Savings Water Disposal Savings Ancillary Material Cost Savings Water Consumption Savings
01 2.1133: Adjust burners for efficient operation $24,100 - $24,100
411,264
kWh
- - - - - -
02 2.1311: Replace electrically-operated equipment with fossil fuel equipment $19,686 $63,600 $23,697
404,380
kWh
$1,063
-
kW-mo/yr
- $(-5,074.0)
-
MMBtu
- - -
03 2.2696: Use excess cold process fluid for industrial cooling needs $1,324 $2,600 $(-717.0)
(-12,238)
kWh
- - - $505
-
Tgal
- $1,536
-
Tgal
04 2.7111: Reduce illumination to minimum necessary levels $2,036 $1,800 $1,519
25,920
kWh
$89
-
kW-mo/yr
- - - $428 -
05 2.3212: Optimize plant power factor $1,263 $4,125 - - $1,263 - - - -
TOTAL RECOMMENDED $48,409 $72,125 $48,599
829,326
kWh
$1,152
-
kW-mo/yr
$1,263 $(-5,074.0)
-
MMBtu
$505
-
Tgal
$428 $1,536
-
Tgal
TOTAL IMPLEMENTED - - - - - - - - -
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs