Assessment Year | 2021 |
---|---|
Principal Product | Silicone Tapes and Laminates |
NAICS | 326130: Laminated Plastics Plate, Sheet (except Packaging), and Shape Manufacturing |
SIC | 3083: Laminated Plastics Plate, Sheet, and Profile Shapes |
Sales Range | $50 M to 100M |
# of Employees | 150 |
Plant Area |
125,000
ft2
|
Annual Production | 8,840
thousand feet
|
Production Hrs. Annual | 8,694
hrs
|
Location (State) | Delaware |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | ||
---|---|---|---|---|---|
Electricity Usage | $538,435 | 7,727,058 |
kWh
|
$0.070 | |
Electricity Demand | $88,826 | 17,475 |
kW-mo/yr
|
$5.08 | |
Natural Gas | $314,873 | 47,639 |
MMBtu
|
$6.61 | |
Waste Disposal Costs | |||||
Water Usage | $19,367 | 3,904 |
Tgal
|
$4.96 | |
Water Disposal | $84,862 | 13,200 |
Tgal
|
$6.43 | |
TOTAL YEARLY COSTS | $1,046,363 | ||||
RECOMMENDED SAVINGS* | $171,005 |
See individual recommendations below
*Non-energy impacts included in savings.
|
|||
IMPLEMENTED SAVINGS* | $160,805 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Natural Gas Savings | Water Usage Savings |
---|---|---|---|---|---|---|---|
01 | 2.7243: Improve air circulation with destratification fans / other methods | $22,950 | $5,445 |
$22,950
283,300
kWh
|
- | - | |
02 | 2.7226: Use computer programs to optimize hvac performance | $3,870 | - |
$3,870
47,740
kWh
|
- | - | |
03 | 2.6212: Turn off equipment during breaks, reduce operating time | $5,030 | $532 |
$5,030
62,130
kWh
|
- | - | |
04 | 3.4114: Replace city water with recycled water via cooling tower | $48,560 | $210,000 |
$(-870.0)
(-10,737)
kWh
|
- |
$49,430
-
Tgal
|
|
05 | 2.6218: Turn off equipment when not in use | $3,140 | $1,288 |
$3,140
38,750
kWh
|
- | - | |
06 | 2.7261: Install timers and/or thermostats | $520 | $236 |
$160
2,010
kWh
|
$360
-
MMBtu
|
- | |
07 | 2.2437: Recover waste heat from equipment | $3,580 | $5,500 | - |
$3,580
-
MMBtu
|
- | |
08 | 2.4146: Use adjustable frequency drive or multiple speed motors on existing system | $11,950 | $8,214 |
$11,950
147,500
kWh
|
- | - | |
09 | 2.4146: Use adjustable frequency drive or multiple speed motors on existing system | $6,430 | $7,309 |
$6,430
79,410
kWh
|
- | - | |
10 | 2.4146: Use adjustable frequency drive or multiple speed motors on existing system | $3,190 | $6,328 |
$3,190
39,350
kWh
|
- | - | |
11 | 2.7135: Install occupancy sensors | $290 | $270 |
$80
1,010
kWh
|
$210
-
MMBtu
|
- | |
12 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $61,495 | $34,144 |
$61,495
759,202
kWh
|
- | - | |
TOTAL RECOMMENDED | $171,005 | $279,266 |
$117,425
1,449,665
kWh
|
$4,150
-
MMBtu
|
$49,430
-
Tgal
|
||
TOTAL IMPLEMENTED | $160,805 | $265,880 |
$111,015
1,370,555
kWh
|
$360
-
MMBtu
|
$49,430
-
Tgal
|
||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Natural Gas Savings | Water Usage Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs