| Assessment Year | 2021 |
|---|---|
| Principal Product | Treated Waste Water |
| NAICS | 221320: Sewage Treatment Facilities |
| SIC | 4952: Sewerage Systems |
| Sales Range | less than $500 k |
| # of Employees | 11 |
| Plant Area |
440,000
ft2
|
| Annual Production | 418,922
Tgal
|
| Production Hrs. Annual | 8,760
hrs
|
| Location (State) | Delaware |
Facility Energy Cost and Usage
| Source | Yearly Cost | Usage | Unit Cost | |
|---|---|---|---|---|
| Electricity Usage | $186,011 | 3,024,953 |
kWh
|
$0.061 |
| Electricity Demand | $23,369 | 5,512 |
kW-mo/yr
|
$4.24 |
| Electricity Fees | $7,366 | - |
|
- |
| TOTAL YEARLY COSTS | $216,746 | |||
| RECOMMENDED SAVINGS* | $48,490 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
| IMPLEMENTED SAVINGS* | $16,710 | |||
Recommendations
| # | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings |
|---|---|---|---|---|---|
| 01 | 2.4146: Use adjustable frequency drive or multiple speed motors on existing system | $9,360 | $10,000 |
$9,360
140,100
kWh
|
|
| 02 | 2.4146: Use adjustable frequency drive or multiple speed motors on existing system | $9,630 | $10,000 |
$9,630
142,390
kWh
|
|
| 03 | 2.4322: Use or replace with energy efficient substitutes | $13,920 | $100,000 |
$13,920
208,200
kWh
|
|
| 04 | 2.7234: Use heat pump for space conditioning | $12,790 | $35,300 |
$12,790
191,500
kWh
|
|
| 05 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $1,910 | $1,594 |
$1,910
28,580
kWh
|
|
| 06 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $880 | $1,036 |
$880
14,380
kWh
|
|
| TOTAL RECOMMENDED | $48,490 | $157,930 |
$48,490
725,150
kWh
|
||
| TOTAL IMPLEMENTED | $16,710 | $102,630 |
$16,710
251,160
kWh
|
||
| Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | |||
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs