Assessment Year | 2016 |
---|---|
Principal Product | Acrylic Molding Resins |
NAICS | 325211: Plastics Material and Resin Manufacturing |
SIC | 2821: Plastics Materials, Synthetic Resins, and Nonvulcanizable Elastomers |
Sales Range | $100 M to 500M |
# of Employees | 90 |
Plant Area |
205,000
ft2
|
Annual Production | 180,000,000
lb
|
Production Hrs. Annual | 8,760
hrs
|
Location (State) | Pennsylvania |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $2,639,954 | 27,577,200 |
kWh
|
$0.096 |
Natural Gas | $527,855 | 87,560 |
MMBtu
|
$6.03 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $371,700 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $371,700 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Natural Gas Savings | Water Disposal Savings | Other Liquid (non-haz) Savings |
---|---|---|---|---|---|---|---|---|
01 | 3.4114: Replace city water with recycled water via cooling tower | $287,810 | $31,000 | - | - |
$198,450
-
Tgal
|
$89,360
-
gal
|
|
02 | 2.4146: Use adjustable frequency drive or multiple speed motors on existing system | $48,000 | $100,750 |
$48,000
500,000
kWh
|
- | - | - | |
03 | 2.1233: Analyze flue gas for proper air/fuel ratio | $7,300 | $17,825 | - |
$7,300
-
MMBtu
|
- | - | |
04 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $28,590 | $188,100 |
$28,590
297,840
kWh
|
- | - | - | |
TOTAL RECOMMENDED | $371,700 | $337,675 |
$76,590
797,840
kWh
|
$7,300
-
MMBtu
|
$198,450
-
Tgal
|
$89,360
-
gal
|
||
TOTAL IMPLEMENTED | $371,700 | $337,675 |
$76,590
797,840
kWh
|
$7,300
-
MMBtu
|
$198,450
-
Tgal
|
$89,360
-
gal
|
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs