Assessment Year | 2016 |
---|---|
Principal Product | Pharmaceuticals |
NAICS | 325412: Pharmaceutical Preparation Manufacturing |
SIC | 2834: Pharmaceutical Preparations |
Sales Range | less than $500 k |
# of Employees | 260 |
Plant Area |
570,000
ft2
|
Annual Production | 0
units
|
Production Hrs. Annual | 5,000
hrs
|
Location (State) | Delaware |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $1,395,119 | 21,915,639 |
kWh
|
$0.064 |
Electricity Demand | $556,698 | 49,574 |
kW-mo/yr
|
$11.23 |
Electricity Fees | $685 | - |
|
- |
Natural Gas | $661,508 | 115,823 |
MMBtu
|
$5.71 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $591,117 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $481,517 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Administrative Changes Savings |
---|---|---|---|---|---|---|---|---|
01 | 2.4224: Upgrade controls on compressors | $1,270 | $60 |
$1,270
19,868
kWh
|
- | - | - | |
02 | 2.7314: Reduce ventilation air | $310,823 | $38,750 |
$75,023
1,172,244
kWh
|
- |
$235,800
-
MMBtu
|
- | |
03 | 2.1233: Analyze flue gas for proper air/fuel ratio | $7,940 | $1,480 | - | - |
$7,940
-
MMBtu
|
- | |
04 | 2.4321: Upgrade obsolete equipment | $13,830 | $11,600 | - | - | - | $13,830 | |
05 | 2.7423: Reduce heat gain by window tinting | $54,090 | $104,500 |
$54,090
845,131
kWh
|
- | - | - | |
06 | 2.4146: Use adjustable frequency drive or multiple speed motors on existing system | $86,560 | $331,000 |
$86,560
1,352,560
kWh
|
- | - | - | |
07 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $96,070 | $380,000 |
$65,750
1,027,290
kWh
|
$30,320
-
kW-mo/yr
|
- | - | |
08 | 2.2492: Use "heat wheel" or other heat exchanger to cross-exchange building exhaust air with make-up air | $20,534 | $96,100 |
$10,850
169,563
kWh
|
- |
$9,684
-
MMBtu
|
- | |
TOTAL RECOMMENDED | $591,117 | $963,490 |
$293,543
4,586,656
kWh
|
$30,320
-
kW-mo/yr
|
$253,424
-
MMBtu
|
$13,830 | ||
TOTAL IMPLEMENTED | $481,517 | $619,350 |
$205,713
3,214,228
kWh
|
$30,320
-
kW-mo/yr
|
$245,484
-
MMBtu
|
- | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Administrative Changes Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs