| Assessment Year | 2015 |
|---|---|
| Principal Product | Baked Products |
| NAICS | 311812: Commercial Bakeries |
| SIC | 2051: Bread and Other Bakery Products, Except Cookies and Crackers |
| Sales Range | $50 M to 100M |
| # of Employees | 480 |
| Plant Area |
172,000
ft2
|
| Annual Production | 45,000
ton
|
| Production Hrs. Annual | 8,760
hrs
|
| Location (State) | New Jersey |
Facility Energy Cost and Usage
| Source | Yearly Cost | Usage | Unit Cost | |
|---|---|---|---|---|
| Electricity Usage | $1,000,182 | 9,676,000 |
kWh
|
$0.10 |
| Electricity Demand | $133,879 | 20,823 |
kW-mo/yr
|
$6.43 |
| Electricity Fees | $10,138 | - |
|
- |
| Natural Gas | $981,959 | 135,111 |
MMBtu
|
$7.27 |
| TOTAL YEARLY COSTS | - | |||
| RECOMMENDED SAVINGS* | $280,860 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
| IMPLEMENTED SAVINGS* | $174,945 | |||
Recommendations
| # | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings |
|---|---|---|---|---|---|---|---|
| 01 | 2.7314: Reduce ventilation air | $169,710 | - |
$23,960
232,620
kWh
|
$2,060
-
kW-mo/yr
|
$143,690
-
MMBtu
|
|
| 02 | 2.2437: Recover waste heat from equipment | $16,140 | $5,060 | - | - |
$16,140
-
MMBtu
|
|
| 03 | 2.4322: Use or replace with energy efficient substitutes | $5,235 | $3,000 |
$4,760
46,200
kWh
|
$475
-
kW-mo/yr
|
- | |
| 04 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $60,305 | $98,895 |
$55,520
539,000
kWh
|
$4,785
-
kW-mo/yr
|
- | |
| 05 | 2.7135: Install occupancy sensors | $3,810 | $1,640 |
$3,510
34,080
kWh
|
$300
-
kW-mo/yr
|
- | |
| 06 | 2.2414: Use waste heat from hot flue gases to preheat | $25,660 | $74,190 | - | - |
$25,660
-
MMBtu
|
|
| TOTAL RECOMMENDED | $280,860 | $182,785 |
$87,750
851,900
kWh
|
$7,620
-
kW-mo/yr
|
$185,490
-
MMBtu
|
||
| TOTAL IMPLEMENTED | $174,945 | $3,000 |
$28,720
278,820
kWh
|
$2,535
-
kW-mo/yr
|
$143,690
-
MMBtu
|
||
| Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | |||
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs