| Assessment Year | 2014 |
|---|---|
| Principal Product | newspapers |
| NAICS | 323111: Commercial Printing (except Screen and Books) |
| SIC | 2711: Newspapers: Publishing, or Publishing and Printing |
| Sales Range | $500 k to 1M |
| # of Employees | 100 |
| Plant Area |
86,395
ft2
|
| Annual Production | 20,000,000
pieces
|
| Production Hrs. Annual | 8,760
hrs
|
| Location (State) | Pennsylvania |
Facility Energy Cost and Usage
| Source | Yearly Cost | Usage | Unit Cost | |
|---|---|---|---|---|
| Electricity Usage | $340,497 | 4,835,645 |
kWh
|
$0.070 |
| Natural Gas | $20,493 | 2,145 |
MMBtu
|
$9.55 |
| TOTAL YEARLY COSTS | - | |||
| RECOMMENDED SAVINGS* | $112,620 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
| IMPLEMENTED SAVINGS* | - | |||
Recommendations
| # | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Natural Gas Savings |
|---|---|---|---|---|---|---|
| 01 | 2.7316: Centralize control of exhaust fans to ensure their shutdown, or establish program to ensure manual shutdown | $31,300 | - |
$31,300
447,000
kWh
|
- | |
| 02 | 2.7221: Lower temperature during the winter season and vice-versa | $5,700 | - |
$5,700
81,200
kWh
|
- | |
| 03 | 2.7229: Air condition only space necessary | $22,620 | $750 |
$22,620
323,200
kWh
|
- | |
| 04 | 2.4146: Use adjustable frequency drive or multiple speed motors on existing system | $19,400 | $13,500 |
$19,400
278,000
kWh
|
- | |
| 05 | 2.7447: Install vinyl strip / high speed / air curtain doors | $7,400 | $28,000 | - |
$7,400
-
MMBtu
|
|
| 06 | 2.2437: Recover waste heat from equipment | $4,750 | $1,300 |
$1,850
26,500
kWh
|
$2,900
-
MMBtu
|
|
| 07 | 2.2437: Recover waste heat from equipment | $4,960 | $1,400 |
$4,960
70,900
kWh
|
- | |
| 08 | 2.7135: Install occupancy sensors | $3,460 | $3,210 |
$3,460
49,400
kWh
|
- | |
| 09 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $11,200 | $18,600 |
$11,200
160,000
kWh
|
- | |
| 10 | 2.6218: Turn off equipment when not in use | $1,830 | - |
$460
6,540
kWh
|
$1,370
-
MMBtu
|
|
| TOTAL RECOMMENDED | $112,620 | $66,760 |
$100,950
1,442,740
kWh
|
$11,670
-
MMBtu
|
||
| TOTAL IMPLEMENTED | - | - | - | - | ||
| Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Natural Gas Savings | |||
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs