| Assessment Year | 2012 |
|---|---|
| Principal Product | Aluminium Enclosures |
| NAICS | 332999: All Other Miscellaneous Fabricated Metal Product Manufacturing |
| SIC | 3499: Fabricated Metal Products, Not Elsewhere Classified |
| Sales Range | $5 M to 10M |
| # of Employees | 82 |
| Plant Area |
52,000
ft2
|
| Annual Production | 500,000
pieces
|
| Production Hrs. Annual | 2,142
hrs
|
| Location (State) | Maryland |
Facility Energy Cost and Usage
| Source | Yearly Cost | Usage | Unit Cost | |
|---|---|---|---|---|
| Electricity Usage | $100,225 | 1,043,647 |
kWh
|
$0.096 |
| Natural Gas | $20,507 | 1,522 |
MMBtu
|
$13.47 |
| TOTAL YEARLY COSTS | - | |||
| RECOMMENDED SAVINGS* | $16,906 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
| IMPLEMENTED SAVINGS* | $8,114 | |||
Recommendations
| # | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Natural Gas Savings |
|---|---|---|---|---|---|---|
| 01 | 2.7226: Use computer programs to optimize hvac performance | $7,140 | $100 |
$7,140
73,600
kWh
|
- | |
| 02 | 2.7231: Use radiant heater for spot heating | $2,870 | $818 | - |
$2,870
-
MMBtu
|
|
| 03 | 2.7221: Lower temperature during the winter season and vice-versa | $1,360 | $50 |
$1,360
14,000
kWh
|
- | |
| 04 | 2.7312: Minimize use of outside make-up air for ventilation except when used for economizer cycle | $1,680 | $5,000 |
$1,680
17,500
kWh
|
- | |
| 05 | 2.7314: Reduce ventilation air | $1,102 | $600 |
$119
1,218
kWh
|
$983
-
MMBtu
|
|
| 06 | 2.7313: Recycle air for heating, ventilation and air conditioning | $940 | $230 |
$100
1,050
kWh
|
$840
-
MMBtu
|
|
| 07 | 2.7316: Centralize control of exhaust fans to ensure their shutdown, or establish program to ensure manual shutdown | $360 | $20 | - |
$360
-
MMBtu
|
|
| 08 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $974 | $480 |
$974
10,043
kWh
|
- | |
| 09 | 2.2523: Reduce infiltration to refrigerated areas; isolate hot equipment from refrigerated areas | $480 | $425 |
$480
4,960
kWh
|
- | |
| TOTAL RECOMMENDED | $16,906 | $7,723 |
$11,853
122,371
kWh
|
$5,053
-
MMBtu
|
||
| TOTAL IMPLEMENTED | $8,114 | $580 |
$8,114
83,643
kWh
|
- | ||
| Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Natural Gas Savings | |||
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs