Assessment Year 2010
Principal Product PEST CONTROL
NAICS 325320: Pesticide and Other Agricultural Chemical Manufacturing
SIC 3496: Miscellaneous Fabricated Wire Products
Sales Range $10
M
to 50
M
# of Employees 225
Plant Area 200,000
ft2
Annual Production 40,350,000
pieces
Production Hrs. Annual 6,240
hrs
Location (State) Pennsylvania

Facility Energy Cost and Usage

Source Yearly Cost Usage
Electricity Usage $247,094 3,873,976
kWh
Electricity Demand $82,114 901
kW-mo/yr
Electricity Fees $14,367 -
Natural Gas $172,667 13,807
MMBtu
TOTAL YEARLY COSTS -
RECOMMENDED SAVINGS* $69,293 *Non-energy impacts included in savings.
IMPLEMENTED SAVINGS* $44,359

Recommendations

# Description Yearly Savings* Imp'd Cost* Status Electricity Usage Savings Natural Gas Savings
01 2.7314: Reduce ventilation air $4,400 $100 - $4,400
-
MMBtu
02 2.6218: Turn off equipment when not in use $1,660 $100 $1,660
18,600
kWh
-
03 2.7122: Disconnect ballasts $655 $5,000 $655
7,363
kWh
-
04 2.7491: Insulate glazing, walls, ceilings, and roofs $8,400 $5,200 - $8,400
-
MMBtu
05 2.7131: Add area lighting switches $23,365 $120 $23,365
262,530
kWh
-
06 2.4111: Utilize energy-efficient belts and other improved mechanisms $414 $440 $414
4,650
kWh
-
07 2.7491: Insulate glazing, walls, ceilings, and roofs $2,800 $2,400 - $2,800
-
MMBtu
08 2.2511: Insulate bare equipment $246 $400 - $246
-
MMBtu
09 2.1122: Re-size charging openings or add a movable door on equipment $438 $1,100 - $438
-
MMBtu
10 2.7142: Utilize higher efficiency lamps and/or ballasts $18,529 $47,000 $18,529
208,191
kWh
-
11 2.7491: Insulate glazing, walls, ceilings, and roofs $4,440 $13,400 $340
3,800
kWh
$4,100
-
MMBtu
12 2.2437: Recover waste heat from equipment $1,690 $5,550 - $1,690
-
MMBtu
13 2.7243: Improve air circulation with destratification fans / other methods $860 $8,000 $(-170.0)
(-1,920)
kWh
$1,030
-
MMBtu
14 2.7142: Utilize higher efficiency lamps and/or ballasts $1,396 $20,804 $1,396
15,683
kWh
-
TOTAL RECOMMENDED $69,293 $109,614 $46,189
518,897
kWh
$23,104
-
MMBtu
TOTAL IMPLEMENTED $44,359 $73,364 $44,359
498,417
kWh
-
Yearly Savings* Imp'd Cost* Electricity Usage Savings Natural Gas Savings
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs