Assessment Year | 2007 |
---|---|
Principal Product | non-alcoholic carbonated beverages |
NAICS | 312111: Soft Drink Manufacturing |
SIC | 2086: Bottled and Canned Soft Drinks and Carbonated Waters |
Sales Range | $50 M to 100M |
# of Employees | 60 |
Plant Area |
150,000
ft2
|
Annual Production | 10,000,000
units
|
Production Hrs. Annual | 6,240
hrs
|
Location (State) | Delaware |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $358,951 | 4,170,861 |
kWh
|
$0.086 |
Electricity Demand | $3,940 | 949 |
kW-mo/yr
|
$4.15 |
Electricity Fees | $8,992 | - |
|
- |
Natural Gas | $212,998 | 39,452 |
MMBtu
|
$5.40 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $168,808 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $120,247 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Natural Gas Savings | Water Consumption Savings |
---|---|---|---|---|---|---|---|
01 | 2.2437: Recover waste heat from equipment | $40,014 | $14,000 | - |
$40,014
-
MMBtu
|
- | |
02 | 2.1224: Replace boiler | $33,159 | $102,000 | - |
$33,159
-
MMBtu
|
- | |
03 | 2.8114: Change rate schedules or other changes in utility service | $31,900 | - |
$31,900
-
kWh
|
- | - | |
04 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $20,801 | $175,000 |
$20,801
224,440
kWh
|
- | - | |
05 | 3.4156: Use flow control valves on equipment to optimize water use | $18,000 | $1,000 | - | - |
$18,000
-
Tgal
|
|
06 | 2.1224: Replace boiler | $12,509 | $27,400 | - |
$12,509
-
MMBtu
|
- | |
07 | 2.4111: Utilize energy-efficient belts and other improved mechanisms | $4,978 | $2,105 |
$4,978
70,197
kWh
|
- | - | |
08 | 2.2531: Re-size charging openings or add movable cover or door | $3,800 | $900 | - |
$3,800
-
MMBtu
|
- | |
09 | 2.3511: Use plant owned transformers or lease transformers | $2,893 | $14,000 |
$2,893
31,450
kWh
|
- | - | |
10 | 2.7135: Install occupancy sensors | $754 | $285 |
$754
8,200
kWh
|
- | - | |
TOTAL RECOMMENDED | $168,808 | $336,690 |
$61,326
334,287
kWh
|
$89,482
-
MMBtu
|
$18,000
-
Tgal
|
||
TOTAL IMPLEMENTED | $120,247 | $193,290 |
$58,433
302,837
kWh
|
$43,814
-
MMBtu
|
$18,000
-
Tgal
|
||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Natural Gas Savings | Water Consumption Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs