Assessment Year | 2022 |
---|---|
Principal Product | Machine Rail Parts |
NAICS | 334519: Other Measuring and Controlling Device Manufacturing |
SIC | 3599: Industrial and Commercial Machinery and Equipment, Not Elsewhere Classified |
Sales Range | $10 M to 50M |
# of Employees | 170 |
Plant Area |
120,000
ft2
|
Annual Production | 100,000
units
|
Production Hrs. Annual | 8,400
hrs
|
Location (State) | Ohio |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | ||
---|---|---|---|---|---|
Electricity Usage | $90,221 | 2,000,200 |
kWh
|
$0.045 | |
Electricity Demand | $61,661 | 4,195 |
kW-mo/yr
|
$14.70 | |
Electricity Fees | $24,072 | - |
|
- | |
Natural Gas | $20,274 | 3,576 |
MMBtu
|
$5.67 | |
Waste Disposal Costs | |||||
Water Usage | $1,947 | 216 |
Tgal
|
$9.03 | |
Other Liquid (non-haz) | $48,309 | 2,750 |
gal
|
$17.57 | |
TOTAL YEARLY COSTS | $246,483 | ||||
RECOMMENDED SAVINGS* | $48,768 |
See individual recommendations below
*Non-energy impacts included in savings.
|
|||
IMPLEMENTED SAVINGS* | $22,425 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Other Liquid (non-haz) Savings |
---|---|---|---|---|---|---|---|
01 | 2.6212: Turn off equipment during breaks, reduce operating time | $4,804 | - |
$4,804
114,864
kWh
|
- | - | |
02 | 2.4324: Replace hydraulic / pneumatic equipment with electric equipment | $3,402 | $1,640 |
$3,402
81,358
kWh
|
- | - | |
03 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $3,554 | - |
$3,554
84,972
kWh
|
- | - | |
04 | 2.4322: Use or replace with energy efficient substitutes | $1,741 | $613 |
$1,741
41,634
kWh
|
- | - | |
05 | 2.4322: Use or replace with energy efficient substitutes | $8,381 | $6,000 |
$2,696
64,467
kWh
|
$5,685
-
kW-mo/yr
|
- | |
06 | 2.4312: Improve lubrication practices | $21,048 | $10,400 | - | - |
$21,048
-
gal
|
|
07 | 2.1121: Use insulation in furnaces to facilitate heating / cooling | $5,837 | $1,000 |
$5,837
139,581
kWh
|
- | - | |
TOTAL RECOMMENDED | $48,768 | $19,653 |
$22,034
526,877
kWh
|
$5,685
-
kW-mo/yr
|
$21,048
-
gal
|
||
TOTAL IMPLEMENTED | $22,425 | $8,640 |
$16,739
400,271
kWh
|
$5,685
-
kW-mo/yr
|
- | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Other Liquid (non-haz) Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs