| Assessment Year | 2015 |
|---|---|
| Principal Product | Retail Display Fixtures |
| NAICS | 337215: Showcase, Partition, Shelving, and Locker Manufacturing |
| SIC | 2541: Wood Office and Store Fixtures, Partitions, Shelving, and Lockers |
| Sales Range | $10 M to 50M |
| # of Employees | 400 |
| Plant Area |
86,700
ft2
|
| Annual Production | 126,000
pieces
|
| Production Hrs. Annual | 2,741
hrs
|
| Location (State) | Colorado |
Facility Energy Cost and Usage
| Source | Yearly Cost | Usage | Unit Cost | |
|---|---|---|---|---|
| Electricity Usage | $102,356 | 1,729,920 |
kWh
|
$0.059 |
| Electricity Demand | $91,335 | 5,547 |
kW-mo/yr
|
$16.47 |
| Electricity Fees | $2,012 | - |
|
- |
| Natural Gas | $26,754 | 3,388 |
MMBtu
|
$7.90 |
| TOTAL YEARLY COSTS | - | |||
| RECOMMENDED SAVINGS* | $35,640 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
| IMPLEMENTED SAVINGS* | - | |||
Recommendations
| # | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Personnel Changes Savings | Administrative Changes Savings | Ancillary Material Cost Savings |
|---|---|---|---|---|---|---|---|---|---|
| 01 | 2.3191: Use demand controller or load shedder | $7,850 | $20,000 | - |
$7,850
-
kW-mo/yr
|
- | - | - | |
| 02 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $6,630 | $950 |
$4,000
67,600
kWh
|
$2,630
-
kW-mo/yr
|
- | - | - | |
| 03 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $15,680 | $42,100 |
$10,660
180,100
kWh
|
$4,610
-
kW-mo/yr
|
$100 | - | $310 | |
| 04 | 2.8121: Apply for tax-free status for energy purchases | $5,480 | $500 | - | - | - | $5,480 | - | |
| TOTAL RECOMMENDED | $35,640 | $63,550 |
$14,660
247,700
kWh
|
$15,090
-
kW-mo/yr
|
$100 | $5,480 | $310 | ||
| TOTAL IMPLEMENTED | - | - | - | - | - | - | - | ||
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs