Assessment Year | 2010 |
---|---|
Principal Product | units |
NAICS | 333241: Food Product Machinery Manufacturing |
SIC | 3556: Food Products Machinery |
Sales Range | $10 M to 50M |
# of Employees | 180 |
Plant Area |
140,000
ft2
|
Annual Production | 130,000
pieces
|
Production Hrs. Annual | 4,290
hrs
|
Location (State) | Colorado |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $126,882 | 3,186,040 |
kWh
|
$0.040 |
Electricity Demand | $131,631 | 9,040 |
kW-mo/yr
|
$14.56 |
Electricity Fees | $2,779 | - |
|
- |
Natural Gas | $38,700 | 5,167 |
MMBtu
|
$7.49 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $26,180 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $13,090 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Personnel Changes Savings | Ancillary Material Cost Savings |
---|---|---|---|---|---|---|---|---|---|
01 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $6,990 | $920 |
$3,300
87,000
kWh
|
$3,690
-
kW-mo/yr
|
- | - | - | |
02 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $1,550 | $1,000 |
$730
19,200
kWh
|
$820
-
kW-mo/yr
|
- | - | - | |
03 | 2.4111: Utilize energy-efficient belts and other improved mechanisms | $1,100 | $7,610 |
$710
18,700
kWh
|
$390
-
kW-mo/yr
|
- | - | - | |
04 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $4,550 | $41,810 |
$1,720
45,400
kWh
|
$2,230
-
kW-mo/yr
|
- | $80 | $520 | |
05 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $2,720 | $6,380 |
$860
22,600
kWh
|
$1,870
-
kW-mo/yr
|
- | $10 | $(-20.0) | |
06 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $2,630 | $2,690 |
$290
7,700
kWh
|
$170
-
kW-mo/yr
|
- | $990 | $1,180 | |
07 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $2,630 | $16,780 |
$850
22,500
kWh
|
$1,850
-
kW-mo/yr
|
- | $40 | $(-110.0) | |
08 | 2.7243: Improve air circulation with destratification fans / other methods | $2,380 | $14,690 |
$(-380.0)
(-10,100)
kWh
|
$(-210.0)
-
kW-mo/yr
|
$2,970
-
MMBtu
|
- | - | |
09 | 2.7135: Install occupancy sensors | $1,460 | $3,000 |
$1,170
31,100
kWh
|
- | - | $40 | $250 | |
10 | 2.6211: Conserve energy by efficient use of vending machines | $170 | $590 |
$140
3,700
kWh
|
$30
-
kW-mo/yr
|
- | - | - | |
TOTAL RECOMMENDED | $26,180 | $95,470 |
$9,390
247,800
kWh
|
$10,840
-
kW-mo/yr
|
$2,970
-
MMBtu
|
$1,160 | $1,820 | ||
TOTAL IMPLEMENTED | $13,090 | $43,730 |
$5,750
151,600
kWh
|
$6,740
-
kW-mo/yr
|
- | $80 | $520 | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Personnel Changes Savings | Ancillary Material Cost Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs