Assessment Year | 2007 |
---|---|
Principal Product | Wood Doors & Architectural Millwork |
NAICS | 321911: Wood Window and Door Manufacturing |
SIC | 2431: Millwork |
Sales Range | $10 M to 50M |
# of Employees | 120 |
Plant Area |
70,000
ft2
|
Annual Production | 18,000
pieces
|
Production Hrs. Annual | 4,680
hrs
|
Location (State) | Colorado |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $50,364 | 1,496,960 |
kWh
|
$0.034 |
Electricity Demand | $76,273 | 5,359 |
kW-mo/yr
|
$14.23 |
Electricity Fees | $322 | - |
|
- |
Natural Gas | $8,146 | 1,000 |
MMBtu
|
$8.15 |
Fuel Oil #2 | $88,400 | 4,267 |
MMBtu
|
$20.72 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $25,267 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $4,797 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Fuel Oil #2 Savings | Ancillary Material Cost Savings |
---|---|---|---|---|---|---|---|---|
01 | 2.4146: Use adjustable frequency drive or multiple speed motors on existing system | $12,270 | $89,570 |
$4,680
195,100
kWh
|
$7,590
-
kW-mo/yr
|
- | - | |
02 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $3,220 | $610 |
$1,720
71,900
kWh
|
$1,500
-
kW-mo/yr
|
- | - | |
03 | 2.6218: Turn off equipment when not in use | $1,460 | - |
$1,460
60,900
kWh
|
- | - | - | |
04 | 2.4231: Reduce the pressure of compressed air to the minimum required | $1,220 | $3,430 |
$660
27,300
kWh
|
$560
-
kW-mo/yr
|
- | - | |
05 | 2.4133: Use most efficient type of electric motors | $117 | $276 |
$45
1,863
kWh
|
$72
-
kW-mo/yr
|
- | - | |
06 | 2.8226: Increase efficiency of trucks | $5,040 | - | - | - |
$5,040
-
MMBtu
|
- | |
07 | 2.9114: Use solar heat to make electricty | $1,290 | $11,000 |
$350
14,600
kWh
|
$940
-
kW-mo/yr
|
- | - | |
08 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $600 | $2,270 |
$150
6,100
kWh
|
$470
-
kW-mo/yr
|
- | $(-20.0) | |
09 | 2.7135: Install occupancy sensors | $50 | $200 |
$30
1,200
kWh
|
$20
-
kW-mo/yr
|
- | - | |
TOTAL RECOMMENDED | $25,267 | $107,356 |
$9,095
378,963
kWh
|
$11,152
-
kW-mo/yr
|
$5,040
-
MMBtu
|
$(-20.0) | ||
TOTAL IMPLEMENTED | $4,797 | $886 |
$3,225
134,663
kWh
|
$1,572
-
kW-mo/yr
|
- | - | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Fuel Oil #2 Savings | Ancillary Material Cost Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs