| Assessment Year | 2005 |
|---|---|
| Principal Product | Aircraft |
| NAICS | 336413: Other Aircraft Parts and Auxiliary Equipment Manufacturing |
| SIC | 3728: Aircraft Parts and Auxiliary Equipment, Not Elsewhere Classified |
| Sales Range | $5 M to 10M |
| # of Employees | 400 |
| Plant Area |
90,000
ft2
|
| Annual Production | 7
pieces
|
| Production Hrs. Annual | 6,916
hrs
|
| Location (State) | New Mexico |
Facility Energy Cost and Usage
| Source | Yearly Cost | Usage | Unit Cost | |
|---|---|---|---|---|
| Electricity Usage | $115,357 | 1,752,960 |
kWh
|
$0.066 |
| Electricity Demand | $11,817 | 3,540 |
kW-mo/yr
|
$3.34 |
| Electricity Fees | $2,392 | - |
|
- |
| Natural Gas | $6,747 | 775 |
MMBtu
|
$8.71 |
| TOTAL YEARLY COSTS | - | |||
| RECOMMENDED SAVINGS* | $19,950 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
| IMPLEMENTED SAVINGS* | - | |||
Recommendations
| # | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Personnel Changes Savings | Ancillary Material Cost Savings |
|---|---|---|---|---|---|---|---|---|---|
| 01 | 2.7145: Install skylights | $9,660 | $40,800 |
$7,150
175,500
kWh
|
$1,530
-
kW-mo/yr
|
- | $870 | $110 | |
| 02 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $3,460 | $7,700 |
$2,790
68,500
kWh
|
$390
-
kW-mo/yr
|
- | $140 | $140 | |
| 03 | 2.9111: Use solar heat to heat make-up air | $2,480 | $30,770 |
$(-310.0)
(-7,600)
kWh
|
$(-80.0)
-
kW-mo/yr
|
$2,870
-
MMBtu
|
- | - | |
| 04 | 2.7135: Install occupancy sensors | $2,420 | $7,570 |
$1,640
40,200
kWh
|
- | - | $80 | $700 | |
| 05 | 2.7243: Improve air circulation with destratification fans / other methods | $1,370 | $1,000 |
$(-200.0)
(-4,900)
kWh
|
$(-30.0)
-
kW-mo/yr
|
$1,600
-
MMBtu
|
- | - | |
| 06 | 2.7135: Install occupancy sensors | $560 | $1,760 |
$560
13,800
kWh
|
- | - | - | - | |
| TOTAL RECOMMENDED | $19,950 | $89,600 |
$11,630
285,500
kWh
|
$1,810
-
kW-mo/yr
|
$4,470
-
MMBtu
|
$1,090 | $950 | ||
| TOTAL IMPLEMENTED | - | - | - | - | - | - | - | ||
| Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Personnel Changes Savings | Ancillary Material Cost Savings | |||
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs