Assessment Year | 2005 |
---|---|
Principal Product | Printed circuir boards |
NAICS | 334412: Bare Printed Circuit Board Manufacturing |
SIC | 3672: Printed Circuit Boards |
Sales Range | $10 M to 50M |
# of Employees | 125 |
Plant Area |
31,000
ft2
|
Annual Production | 13,000
pieces
|
Production Hrs. Annual | 6,032
hrs
|
Location (State) | Colorado |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $112,393 | 3,510,778 |
kWh
|
$0.032 |
Electricity Demand | $106,115 | 7,842 |
kW-mo/yr
|
$13.53 |
Electricity Fees | $203 | - |
|
- |
Natural Gas | $22,746 | 2,790 |
MMBtu
|
$8.15 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $17,910 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $4,910 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Water Disposal Savings | Personnel Changes Savings | Ancillary Material Cost Savings | Water Consumption Savings |
---|---|---|---|---|---|---|---|---|---|---|---|
01 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $1,270 | $210 |
$800
24,200
kWh
|
$470
-
kW-mo/yr
|
- | - | - | - | - | |
02 | 2.4133: Use most efficient type of electric motors | $280 | $420 |
$150
4,616
kWh
|
$130
-
kW-mo/yr
|
- | - | - | - | - | |
03 | 3.4156: Use flow control valves on equipment to optimize water use | $1,090 | $1,990 | - | - | - |
$630
-
Tgal
|
- | - |
$460
-
Tgal
|
|
04 | 2.4239: Eliminate or reduce compressed air usage | $850 | $1,310 |
$420
12,800
kWh
|
$430
-
kW-mo/yr
|
- | - | - | - | - | |
05 | 2.2711: Utilize outside air instead of conditioned air for drying | $680 | $340 |
$420
12,800
kWh
|
$260
-
kW-mo/yr
|
- | - | - | - | - | |
06 | 2.2426: Use waste heat from flue gases to heat space conditioning air | $7,880 | $8,110 |
$(-190.0)
(-5,600)
kWh
|
$(-160.0)
-
kW-mo/yr
|
$8,230
-
MMBtu
|
- | - | - | - | |
07 | 2.7145: Install skylights | $3,180 | $19,200 |
$1,280
38,700
kWh
|
$1,800
-
kW-mo/yr
|
- | - | $(-10.0) | $110 | - | |
08 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $2,070 | $5,110 |
$1,050
31,900
kWh
|
$900
-
kW-mo/yr
|
- | - | $70 | $50 | - | |
09 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $610 | $1,210 |
$140
4,100
kWh
|
$90
-
kW-mo/yr
|
- | - | $220 | $160 | - | |
TOTAL RECOMMENDED | $17,910 | $37,900 |
$4,070
123,516
kWh
|
$3,920
-
kW-mo/yr
|
$8,230
-
MMBtu
|
$630
-
Tgal
|
$280 | $320 |
$460
-
Tgal
|
||
TOTAL IMPLEMENTED | $4,910 | $7,290 |
$2,560
77,616
kWh
|
$1,850
-
kW-mo/yr
|
- | - | $290 | $210 | - | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Water Disposal Savings | Personnel Changes Savings | Ancillary Material Cost Savings | Water Consumption Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs