Assessment Year | 2003 |
---|---|
Principal Product | Finished household furniture |
NAICS | 337122: Nonupholstered Wood Household Furniture Manufacturing |
SIC | 2511: Wood Household Furniture, Except Upholstered |
Sales Range | $5 M to 10M |
# of Employees | 72 |
Plant Area |
36,000
ft2
|
Annual Production | 822
thousand feet
|
Production Hrs. Annual | 6,240
hrs
|
Location (State) | Montana |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $50,699 | 1,230,800 |
kWh
|
$0.041 |
Electricity Demand | $23,157 | 2,883 |
kW-mo/yr
|
$8.03 |
Electricity Fees | $96 | - |
|
- |
Natural Gas | $19,142 | 3,676 |
MMBtu
|
$5.21 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $71,989 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $4,530 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Ancillary Material Cost Savings | Increase in Production Savings |
---|---|---|---|---|---|---|---|---|---|
01 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $6,720 | $16,720 |
$5,870
123,000
kWh
|
$1,900
-
kW-mo/yr
|
- | $(-1,050.0) | - | |
02 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $4,530 | $1,050 |
$3,420
71,700
kWh
|
$1,110
-
kW-mo/yr
|
- | - | - | |
03 | 2.2492: Use "heat wheel" or other heat exchanger to cross-exchange building exhaust air with make-up air | $3,380 | $8,630 |
$(-420.0)
(-8,700)
kWh
|
$(-140.0)
-
kW-mo/yr
|
$3,940
-
MMBtu
|
- | - | |
04 | 2.6212: Turn off equipment during breaks, reduce operating time | $3,310 | $870 |
$3,310
69,300
kWh
|
- | - | - | - | |
05 | 2.2437: Recover waste heat from equipment | $2,750 | $1,410 | - | - |
$2,750
-
MMBtu
|
- | - | |
06 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $1,299 | $132 |
$983
20,592
kWh
|
$316
-
kW-mo/yr
|
- | - | - | |
07 | 4.424: Improve space comfort conditioning | $50,000 | $301,060 | - | - | - | - | $50,000 | |
TOTAL RECOMMENDED | $71,989 | $329,872 |
$13,163
275,892
kWh
|
$3,186
-
kW-mo/yr
|
$6,690
-
MMBtu
|
$(-1,050.0) | $50,000 | ||
TOTAL IMPLEMENTED | $4,530 | $1,050 |
$3,420
71,700
kWh
|
$1,110
-
kW-mo/yr
|
- | - | - | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Ancillary Material Cost Savings | Increase in Production Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs