Assessment Year | 2003 |
---|---|
Principal Product | Lumber |
NAICS | 321912: Cut Stock, Resawing Lumber, and Planing |
SIC | 2421: Sawmills and Planing Mills, General |
Sales Range | $10 M to 50M |
# of Employees | 100 |
Plant Area |
56,500
ft2
|
Annual Production | 56,261,000
thousand feet
|
Production Hrs. Annual | 4,420
hrs
|
Location (State) | South Dakota |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $479,990 | 11,256,995 |
kWh
|
$0.043 |
Electricity Demand | $178,050 | 29,775 |
kW-mo/yr
|
$5.98 |
Electricity Fees | $1,248 | - |
|
- |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $78,634 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $62,334 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Ancillary Material Cost Savings |
---|---|---|---|---|---|---|---|
01 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $26,130 | $1,920 |
$21,830
526,100
kWh
|
$4,300
-
kW-mo/yr
|
- | |
02 | 2.4133: Use most efficient type of electric motors | $5,159 | $8,136 |
$3,567
85,980
kWh
|
$1,592
-
kW-mo/yr
|
- | |
03 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $15,150 | $16,560 |
$11,070
266,800
kWh
|
$2,180
-
kW-mo/yr
|
$1,900 | |
04 | 2.4146: Use adjustable frequency drive or multiple speed motors on existing system | $14,910 | - |
$14,910
359,400
kWh
|
- | - | |
05 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $9,183 | $8,431 |
$8,032
193,423
kWh
|
$1,541
-
kW-mo/yr
|
$(-390.0) | |
06 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $5,860 | $4,972 |
$3,544
85,289
kWh
|
$707
-
kW-mo/yr
|
$1,609 | |
07 | 2.4111: Utilize energy-efficient belts and other improved mechanisms | $1,150 | $3,540 |
$790
19,100
kWh
|
$360
-
kW-mo/yr
|
- | |
08 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $1,092 | $1,126 |
$1,107
26,673
kWh
|
$222
-
kW-mo/yr
|
$(-237.0) | |
TOTAL RECOMMENDED | $78,634 | $44,685 |
$64,850
1,562,765
kWh
|
$10,902
-
kW-mo/yr
|
$2,882 | ||
TOTAL IMPLEMENTED | $62,334 | $24,585 |
$52,990
1,276,865
kWh
|
$8,362
-
kW-mo/yr
|
$982 | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Ancillary Material Cost Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs