Assessment Year | 2001 |
---|---|
Principal Product | Bread and rolls |
NAICS |
n/a
|
SIC | 2051: Bread and Other Bakery Products, Except Cookies and Crackers |
Sales Range | $10 M to 50M |
# of Employees | 60 |
Plant Area |
65,917
ft2
|
Annual Production | 18,200,000
lb
|
Production Hrs. Annual | 6,760
hrs
|
Location (State) | New Mexico |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $165,951 | 4,250,400 |
kWh
|
$0.039 |
Electricity Demand | $38,170 | 8,962 |
kW-mo/yr
|
$4.26 |
Electricity Fees | $77,328 | - |
|
- |
Natural Gas | $196,948 | 33,223 |
MMBtu
|
$5.93 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $19,130 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | - |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Personnel Changes Savings | Ancillary Material Cost Savings |
---|---|---|---|---|---|---|---|---|---|
01 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $10,850 | $630 | n/a |
$5,560
144,100
kWh
|
$6,270
-
kW-mo/yr
|
- | - | $(-980.0) |
02 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $4,380 | $170 | n/a |
$3,680
95,400
kWh
|
$1,480
-
kW-mo/yr
|
- | $(-780.0) | - |
03 | 2.4133: Use most efficient type of electric motors | $180 | $359 | n/a |
$101
2,620
kWh
|
$79
-
kW-mo/yr
|
- | - | - |
04 | 2.1213: Direct warmest air to combustion intake | $1,240 | $3,630 | n/a | - | - |
$1,240
-
MMBtu
|
- | - |
05 | 2.7121: Utilize daylight whenever possible in lieu of artificial light | $950 | $1,130 | n/a |
$580
11,900
kWh
|
$370
-
kW-mo/yr
|
- | - | - |
06 | 2.4226: Use / purchase optimum sized compressor | $870 | $2,860 | n/a |
$870
23,500
kWh
|
- | - | - | - |
07 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $660 | - | n/a |
$2,840
73,600
kWh
|
$1,190
-
kW-mo/yr
|
- | $(-770.0) | $(-2,600.0) |
TOTAL RECOMMENDED | $19,130 | $8,779 |
$13,631
351,120
kWh
|
$9,389
-
kW-mo/yr
|
$1,240
-
MMBtu
|
$(-1,550.0) | $(-3,580.0) | ||
TOTAL IMPLEMENTED | - | - | - | - | - | - | - | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Personnel Changes Savings | Ancillary Material Cost Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs