Assessment Year | 2001 |
---|---|
Principal Product | Desiccants |
NAICS |
n/a
|
SIC | 3295: Minerals and Earths, Ground or Otherwise Treated |
Sales Range | $10 M to 50M |
# of Employees | 130 |
Plant Area |
147,000
ft2
|
Annual Production | 810,000,000
pieces
|
Production Hrs. Annual | 6,240
hrs
|
Location (State) | New Mexico |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $280,871 | 5,519,176 |
kWh
|
$0.051 |
Electricity Demand | $54,076 | 1,054 |
kW-mo/yr
|
$51.31 |
Electricity Fees | $80,618 | - |
|
- |
Natural Gas | $203,653 | 32,319 |
MMBtu
|
$6.30 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $41,240 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $22,590 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Water Disposal Savings | Other Liquid (haz) Savings | Personnel Changes Savings | Ancillary Material Cost Savings | By-product Production Savings |
---|---|---|---|---|---|---|---|---|---|---|---|---|
01 | 2.7135: Install occupancy sensors | $7,730 | $35,830 |
$6,640
95,800
kWh
|
$1,090
-
kW-mo/yr
|
- | - | - | - | - | - | |
02 | 2.7135: Install occupancy sensors | $7,010 | $1,600 |
$6,190
100,500
kWh
|
$820
-
kW-mo/yr
|
- | - | - | - | - | - | |
03 | 2.2511: Insulate bare equipment | $2,780 | $1,760 |
$600
6,200
kWh
|
$80
-
kW-mo/yr
|
$2,100
-
MMBtu
|
- | - | - | - | - | |
04 | 2.2511: Insulate bare equipment | $1,500 | $630 | - | - |
$1,500
-
MMBtu
|
- | - | - | - | - | |
05 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $1,290 | - |
$2,520
47,500
kWh
|
$720
-
kW-mo/yr
|
- | - | - | $(-330.0) | $(-1,620.0) | - | |
06 | 2.1213: Direct warmest air to combustion intake | $1,130 | $2,170 | - | - |
$1,130
-
MMBtu
|
- | - | - | - | - | |
07 | 3.5217: Reuse / recycle/ sell paper products | $15,440 | - | - | - | - |
$3,890
-
Tgal
|
- | - | - | $11,550 | |
08 | 3.8132: Use less toxic and volatile solvent substitutes | $4,360 | $4,000 |
$(-210.0)
(-5,300)
kWh
|
$(-90.0)
-
kW-mo/yr
|
- | - |
$5,940
-
gal
|
- | $(-1,280.0) | - | |
TOTAL RECOMMENDED | $41,240 | $45,990 |
$15,740
244,700
kWh
|
$2,620
-
kW-mo/yr
|
$4,730
-
MMBtu
|
$3,890
-
Tgal
|
$5,940
-
gal
|
$(-330.0) | $(-2,900.0) | $11,550 | ||
TOTAL IMPLEMENTED | $22,590 | $4,630 |
$2,310
42,200
kWh
|
$630
-
kW-mo/yr
|
$1,500
-
MMBtu
|
$3,890
-
Tgal
|
$5,940
-
gal
|
$(-330.0) | $(-2,900.0) | $11,550 | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Water Disposal Savings | Other Liquid (haz) Savings | Personnel Changes Savings | Ancillary Material Cost Savings | By-product Production Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs