Assessment Year | 2001 |
---|---|
Principal Product | Surgical and medical instruments and apparatus |
NAICS |
n/a
|
SIC | 3841: Surgical and Medical Instruments and Apparatus |
Sales Range | $1 M to 5M |
# of Employees | 450 |
Plant Area |
225,000
ft2
|
Annual Production | 3,082,500
pieces
|
Production Hrs. Annual | 6,760
hrs
|
Location (State) | New Mexico |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $364,240 | 9,080,400 |
kWh
|
$0.040 |
Electricity Demand | $117,012 | 1,342 |
kW-mo/yr
|
$87.19 |
Electricity Fees | $69,480 | - |
|
- |
Natural Gas | $91,500 | 13,030 |
MMBtu
|
$7.02 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $40,090 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $12,070 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Other Liquid (haz) Savings | Solid Waste (non-haz) Savings |
---|---|---|---|---|---|---|---|---|
01 | 2.7111: Reduce illumination to minimum necessary levels | $5,910 | $3,000 |
$4,220
106,600
kWh
|
$1,690
-
kW-mo/yr
|
- | - | |
02 | 2.3191: Use demand controller or load shedder | $5,300 | $6,000 | - |
$5,300
-
kW-mo/yr
|
- | - | |
03 | 2.4111: Utilize energy-efficient belts and other improved mechanisms | $1,660 | $2,200 |
$1,190
30,000
kWh
|
$470
-
kW-mo/yr
|
- | - | |
04 | 2.6218: Turn off equipment when not in use | $1,650 | - |
$1,650
41,800
kWh
|
- | - | - | |
05 | 2.7124: Make a practice of turning off lights when not needed | $900 | - |
$650
16,400
kWh
|
$250
-
kW-mo/yr
|
- | - | |
06 | 3.8228: Replace heavy metal reagents with non-hazardous reagents | $21,060 | $14,000 | - | - |
$21,060
-
gal
|
- | |
07 | 3.2141: Use cylindrical tanks with height to diameter ratios close to one to reduce wetted surface | $3,610 | $180 | - | - | - |
$3,610
-
lb
|
|
TOTAL RECOMMENDED | $40,090 | $25,380 |
$7,710
194,800
kWh
|
$7,710
-
kW-mo/yr
|
$21,060
-
gal
|
$3,610
-
lb
|
||
TOTAL IMPLEMENTED | $12,070 | $3,180 |
$6,520
164,800
kWh
|
$1,940
-
kW-mo/yr
|
- |
$3,610
-
lb
|
||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Other Liquid (haz) Savings | Solid Waste (non-haz) Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs