| Assessment Year | 1996 |
|---|---|
| Principal Product | agricultural equipment |
| NAICS |
n/a
|
| SIC | 3523: Farm Machinery and Equipment |
| Sales Range | $10 M to 50M |
| # of Employees | 115 |
| Plant Area |
238,000
ft2
|
| Annual Production | 2,000,000
lb
|
| Production Hrs. Annual | 2,340
hrs
|
| Location (State) | Nebraska |
Facility Energy Cost and Usage
| Source | Yearly Cost | Usage | Unit Cost | |
|---|---|---|---|---|
| Electricity Usage | $47,062 | 1,166,471 |
kWh
|
$0.040 |
| Electricity Demand | $18,559 | 2,830 |
kW-mo/yr
|
$6.56 |
| Natural Gas | $12,428 | 2,582 |
MMBtu
|
$4.81 |
| TOTAL YEARLY COSTS | - | |||
| RECOMMENDED SAVINGS* | $11,049 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
| IMPLEMENTED SAVINGS* | $3,072 | |||
Recommendations
| # | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Ancillary Material Cost Savings |
|---|---|---|---|---|---|---|---|---|
| 01 | 2.1311: Replace electrically-operated equipment with fossil fuel equipment | $7,490 | $12,750 |
$7,060
174,678
kWh
|
$5,060
-
kW-mo/yr
|
$(-4,630.0)
-
MMBtu
|
- | |
| 02 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $3,072 | $2,338 |
$1,714
42,497
kWh
|
$1,358
-
kW-mo/yr
|
- | - | |
| 03 | 2.2437: Recover waste heat from equipment | $240 | $300 | - | - |
$240
-
MMBtu
|
- | |
| 04 | 2.4221: Install compressor air intakes in coolest locations | $220 | $520 |
$160
3,810
kWh
|
$60
-
kW-mo/yr
|
- | - | |
| 05 | 2.4133: Use most efficient type of electric motors | $37 | $137 |
$22
879
kWh
|
$15
-
kW-mo/yr
|
- | - | |
| 06 | 2.4231: Reduce the pressure of compressed air to the minimum required | $190 | $60 |
$140
3,517
kWh
|
$50
-
kW-mo/yr
|
- | - | |
| 07 | 3.8132: Use less toxic and volatile solvent substitutes | $(-200.0) | $260 | - | - | - | $(-200.0) | |
| TOTAL RECOMMENDED | $11,049 | $16,365 |
$9,096
225,381
kWh
|
$6,543
-
kW-mo/yr
|
$(-4,390.0)
-
MMBtu
|
$(-200.0) | ||
| TOTAL IMPLEMENTED | $3,072 | $2,338 |
$1,714
42,497
kWh
|
$1,358
-
kW-mo/yr
|
- | - | ||
| Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Ancillary Material Cost Savings | |||
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs