Assessment Year | 1994 |
---|---|
Principal Product | quartz crystals |
NAICS |
n/a
|
SIC | 3679: Electronic Components, Not Elsewhere Classified |
Sales Range | $1 M to 5M |
# of Employees | 125 |
Plant Area |
22,000
ft2
|
Annual Production | 200,000
pieces
|
Production Hrs. Annual | 8,640
hrs
|
Location (State) | Colorado |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $55,850 | 1,083,822 |
kWh
|
$0.052 |
Natural Gas | $5,060 | 1,256 |
MMBtu
|
$4.03 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $21,540 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $6,610 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Natural Gas Savings | Water Disposal Savings | Other Liquid (non-haz) Savings | Other Liquid (haz) Savings |
---|---|---|---|---|---|---|---|---|---|
01 | 3.5314: Use in-process recycling whenever possible | $7,150 | - | - | - | - |
$7,150
-
gal
|
- | |
02 | 2.2614: Use cooling tower or economizer to replace chiller cooling | $4,900 | $3,810 |
$(-190.0)
(-3,517)
kWh
|
- |
$5,090
-
Tgal
|
- | - | |
03 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $3,070 | $6,820 |
$3,070
59,496
kWh
|
- | - | - | - | |
04 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $2,880 | $1,720 |
$2,880
55,979
kWh
|
- | - | - | - | |
05 | 3.5314: Use in-process recycling whenever possible | $1,840 | - | - | - | - | - |
$1,840
-
gal
|
|
06 | 2.7314: Reduce ventilation air | $850 | $550 |
$470
13,775
kWh
|
$380
-
MMBtu
|
- | - | - | |
07 | 2.4133: Use most efficient type of electric motors | $440 | $730 |
$440
8,499
kWh
|
- | - | - | - | |
08 | 2.7211: Clean and maintain refrigerant condensers and towers | $410 | $90 |
$410
7,913
kWh
|
- | - | - | - | |
TOTAL RECOMMENDED | $21,540 | $13,720 |
$7,080
142,145
kWh
|
$380
-
MMBtu
|
$5,090
-
Tgal
|
$7,150
-
gal
|
$1,840
-
gal
|
||
TOTAL IMPLEMENTED | $6,610 | $8,190 |
$4,390
89,683
kWh
|
$380
-
MMBtu
|
- | - |
$1,840
-
gal
|
||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Natural Gas Savings | Water Disposal Savings | Other Liquid (non-haz) Savings | Other Liquid (haz) Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs