Assessment Year 1992
Principal Product Computer Parts
NAICS
n/a
SIC 3499: Fabricated Metal Products, Not Elsewhere Classified
Sales Range $1
M
to 5
M
# of Employees 100
Plant Area 85,000
ft2
Annual Production 144,500
pieces
Production Hrs. Annual 4,477
hrs
Location (State) Colorado

Facility Energy Cost and Usage

Source Yearly Cost Usage
Electricity Usage $79,079 1,254,689
kWh
Natural Gas $8,556 2,134
MMBtu
TOTAL YEARLY COSTS -
RECOMMENDED SAVINGS* $25,670 *Non-energy impacts included in savings.
IMPLEMENTED SAVINGS* -

Recommendations

# Description Yearly Savings* Imp'd Cost* Status Electricity Usage Savings Natural Gas Savings Administrative Changes Savings
01 2.6212: Turn off equipment during breaks, reduce operating time $1,780 $30 $840
13,482
kWh
$940
-
MMBtu
-
02 2.8121: Apply for tax-free status for energy purchases $1,120 $250 - - $1,120
03 2.7231: Use radiant heater for spot heating $530 $200 - $530
-
MMBtu
-
04 2.4221: Install compressor air intakes in coolest locations $480 $100 $480
7,620
kWh
- -
05 2.4224: Upgrade controls on compressors $470 $300 $470
17,878
kWh
- -
06 2.2437: Recover waste heat from equipment $1,100 $2,840 - $1,100
-
MMBtu
-
07 2.7142: Utilize higher efficiency lamps and/or ballasts $430 $220 $430
6,741
kWh
- -
08 2.7243: Improve air circulation with destratification fans / other methods $2,110 $3,200 $(-230.0)
(-3,517)
kWh
$2,340
-
MMBtu
-
09 2.6212: Turn off equipment during breaks, reduce operating time $340 $240 $340
12,896
kWh
- -
10 2.2514: Cover open tanks $370 $360 $370
12,896
kWh
- -
11 2.7142: Utilize higher efficiency lamps and/or ballasts $4,520 $1,060 $4,520
71,805
kWh
- -
12 2.7111: Reduce illumination to minimum necessary levels $3,800 $4,250 $3,800
64,771
kWh
- -
13 2.7142: Utilize higher efficiency lamps and/or ballasts $6,930 $27,850 $6,930
109,906
kWh
- -
14 2.4133: Use most efficient type of electric motors $1,690 $3,100 $1,690
26,671
kWh
- -
TOTAL RECOMMENDED $25,670 $44,000 $19,640
341,149
kWh
$4,910
-
MMBtu
$1,120
TOTAL IMPLEMENTED - - - - -
Yearly Savings* Imp'd Cost* Electricity Usage Savings Natural Gas Savings Administrative Changes Savings
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs