Assessment Year | 1992 |
---|---|
Principal Product | Pressure-Sensitive Tapes |
NAICS |
n/a
|
SIC | 2672: Coated and Laminated Paper, Not Elsewhere Classified |
Sales Range | $10 M to 50M |
# of Employees | 225 |
Plant Area |
400,000
ft2
|
Annual Production | 3,500,000
pieces
|
Production Hrs. Annual | 8,688
hrs
|
Location (State) | Colorado |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $756,018 | 16,283,998 |
kWh
|
$0.046 |
Natural Gas | $337,002 | 149,779 |
MMBtu
|
$2.25 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $58,930 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | - |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Natural Gas Savings | Administrative Changes Savings |
---|---|---|---|---|---|---|---|
01 | 2.4231: Reduce the pressure of compressed air to the minimum required | $6,800 | $20 |
$6,800
146,542
kWh
|
- | - | |
02 | 2.4231: Reduce the pressure of compressed air to the minimum required | $470 | $100 |
$470
10,258
kWh
|
- | - | |
03 | 2.6212: Turn off equipment during breaks, reduce operating time | $2,410 | $100 | - |
$2,410
-
MMBtu
|
- | |
04 | 2.7314: Reduce ventilation air | $4,140 | $1,200 |
$440
17,585
kWh
|
$3,700
-
MMBtu
|
- | |
05 | 2.6212: Turn off equipment during breaks, reduce operating time | $1,350 | $800 |
$1,350
29,015
kWh
|
- | - | |
06 | 2.3137: Use power during off-peak periods | $1,040 | $250 | - | - | $1,040 | |
07 | 2.2511: Insulate bare equipment | $400 | $440 |
$450
9,672
kWh
|
$(-50.0)
-
MMBtu
|
- | |
08 | 2.2437: Recover waste heat from equipment | $2,520 | $2,220 | - |
$2,520
-
MMBtu
|
- | |
09 | 2.7224: Reduce space conditioning during non-working hours | $790 | $900 |
$170
7,034
kWh
|
$620
-
MMBtu
|
- | |
10 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $6,250 | $7,800 |
$6,250
134,525
kWh
|
- | - | |
11 | 2.4133: Use most efficient type of electric motors | $12,430 | $16,710 |
$12,430
267,585
kWh
|
- | - | |
12 | 2.4231: Reduce the pressure of compressed air to the minimum required | $9,150 | $12,000 |
$9,150
196,952
kWh
|
- | - | |
13 | 2.4111: Utilize energy-efficient belts and other improved mechanisms | $9,380 | $13,860 |
$9,380
201,934
kWh
|
- | - | |
14 | 2.4146: Use adjustable frequency drive or multiple speed motors on existing system | $1,800 | $6,820 |
$1,800
38,687
kWh
|
- | - | |
TOTAL RECOMMENDED | $58,930 | $63,220 |
$48,690
1,059,789
kWh
|
$9,200
-
MMBtu
|
$1,040 | ||
TOTAL IMPLEMENTED | - | - | - | - | - | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Natural Gas Savings | Administrative Changes Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs