Assessment Year | 1992 |
---|---|
Principal Product | Computer Peripheral Equipment |
NAICS |
n/a
|
SIC | 3577: Computer Peripheral Equipment, Not Elsewhere Classified |
Sales Range | $50 M to 100M |
# of Employees | 750 |
Plant Area |
250,000
ft2
|
Annual Production | 23,560
pieces
|
Production Hrs. Annual | 2,210
hrs
|
Location (State) | Colorado |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $557,481 | 11,997,949 |
kWh
|
$0.046 |
Natural Gas | $37,917 | 8,598 |
MMBtu
|
$4.41 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $49,099 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $49,099 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Natural Gas Savings | Administrative Changes Savings |
---|---|---|---|---|---|---|---|
01 | 2.2691: Shut off cooling if cold outside air will cool process | $4,930 | $167,000 |
$4,930
106,096
kWh
|
- | - | |
02 | 2.3137: Use power during off-peak periods | $12,960 | $250 | - | - | $12,960 | |
03 | 2.7224: Reduce space conditioning during non-working hours | $4,930 | $2,670 |
$640
41,618
kWh
|
$4,290
-
MMBtu
|
- | |
04 | 2.7314: Reduce ventilation air | $6,040 | $1,270 |
$470
33,998
kWh
|
$5,570
-
MMBtu
|
- | |
05 | 2.1311: Replace electrically-operated equipment with fossil fuel equipment | $10,939 | $8,660 |
$17,624
379,250
kWh
|
$(-6,685.0)
-
MMBtu
|
- | |
06 | 2.1233: Analyze flue gas for proper air/fuel ratio | $450 | $150 | - |
$450
-
MMBtu
|
- | |
07 | 2.6212: Turn off equipment during breaks, reduce operating time | $350 | $300 |
$350
7,620
kWh
|
- | - | |
08 | 2.4133: Use most efficient type of electric motors | $3,410 | $6,230 |
$3,410
73,271
kWh
|
- | - | |
09 | 2.7111: Reduce illumination to minimum necessary levels | $3,900 | $8,300 |
$3,900
259,672
kWh
|
- | - | |
10 | 2.7132: Install timers on light switches in little used areas | $810 | $2,600 |
$810
17,292
kWh
|
- | - | |
11 | 2.2623: Minimize condenser cooling water temperature | $140 | $240 |
$140
9,379
kWh
|
- | - | |
12 | 2.2623: Minimize condenser cooling water temperature | $240 | $1,120 |
$240
16,120
kWh
|
- | - | |
TOTAL RECOMMENDED | $49,099 | $198,790 |
$32,514
944,316
kWh
|
$3,625
-
MMBtu
|
$12,960 | ||
TOTAL IMPLEMENTED | $49,099 | $198,790 |
$32,514
944,316
kWh
|
$3,625
-
MMBtu
|
$12,960 | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Natural Gas Savings | Administrative Changes Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs