Assessment Year | 1991 |
---|---|
Principal Product | ALUMINUM SHEET |
NAICS |
n/a
|
SIC | 3353: Aluminum Sheet, Plate, and Foil |
Sales Range | $50 M to 100M |
# of Employees | 250 |
Plant Area |
n/a
|
Annual Production | 71,000,000
lb
|
Production Hrs. Annual | 8,688
hrs
|
Location (State) | Colorado |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $1,092,513 | 28,852,580 |
kWh
|
$0.038 |
Natural Gas | $1,595,591 | 459,615 |
MMBtu
|
$3.47 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $30,149 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $30,149 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Natural Gas Savings |
---|---|---|---|---|---|---|
01 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $632 | $275 |
$632
16,706
kWh
|
- | |
02 | 2.2443: Re-use or recycle hot or cold process exhaust air | $7,150 | $3,500 | - |
$7,150
-
MMBtu
|
|
03 | 2.4111: Utilize energy-efficient belts and other improved mechanisms | $2,890 | $4,720 |
$2,890
76,202
kWh
|
- | |
04 | 2.4146: Use adjustable frequency drive or multiple speed motors on existing system | $13,080 | $23,725 |
$13,080
345,252
kWh
|
- | |
05 | 2.4133: Use most efficient type of electric motors | $1,897 | $3,595 |
$1,897
99,648
kWh
|
- | |
06 | 2.4131: Size electric motors for peak operating efficiency | $4,500 | $20,650 |
$4,500
118,699
kWh
|
- | |
TOTAL RECOMMENDED | $30,149 | $56,465 |
$22,999
656,507
kWh
|
$7,150
-
MMBtu
|
||
TOTAL IMPLEMENTED | $30,149 | $56,465 |
$22,999
656,507
kWh
|
$7,150
-
MMBtu
|
||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Natural Gas Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs