Assessment Year 1986
Principal Product MILK AND ICE CREAM
NAICS
n/a
SIC 2026: Fluid Milk
Sales Range $10
M
to 50
M
# of Employees 100
Plant Area
n/a
Annual Production 7,500
Tgal
Production Hrs. Annual 7,488
hrs
Location (State) Colorado

Facility Energy Cost and Usage

Source Yearly Cost Usage
Electricity Usage $149,267 2,956,038
kWh
Natural Gas $84,499 18,987
MMBtu
TOTAL YEARLY COSTS -
RECOMMENDED SAVINGS* $64,170 *Non-energy impacts included in savings.
IMPLEMENTED SAVINGS* $35,922

Recommendations

# Description Yearly Savings* Imp'd Cost* Status Electricity Usage Savings Natural Gas Savings
01 2.2121: Increase amount of condensate returned $7,253 $150 - $7,253
-
MMBtu
02 2.1233: Analyze flue gas for proper air/fuel ratio $4,654 $300 - $4,654
-
MMBtu
03 2.4312: Improve lubrication practices $4,524 - $4,524
89,683
kWh
-
04 2.4111: Utilize energy-efficient belts and other improved mechanisms $4,159 $1,800 $4,159
82,356
kWh
-
05 2.2441: Preheat boiler makeup water with waste process heat $6,121 $6,000 - $6,121
-
MMBtu
06 2.4239: Eliminate or reduce compressed air usage $2,221 $800 $2,221
43,962
kWh
-
07 2.2135: Repair and eliminate steam leaks $4,895 $300 - $4,895
-
MMBtu
08 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves $4,811 $150 $4,811
95,252
kWh
-
09 2.2136: Install / repair insulation on steam lines $2,116 $820 - $2,116
-
MMBtu
10 2.2511: Insulate bare equipment $493 $560 $493
9,672
kWh
-
11 2.2523: Reduce infiltration to refrigerated areas; isolate hot equipment from refrigerated areas $3,185 $450 $3,185
63,013
kWh
-
12 2.7221: Lower temperature during the winter season and vice-versa $518 $500 - $518
-
MMBtu
13 2.7221: Lower temperature during the winter season and vice-versa $86 - $86
1,758
kWh
-
14 2.3131: Reschedule plant operations or reduce load to avoid peaks $15,747 $30,000 $15,747
38,687
kWh
-
15 2.7142: Utilize higher efficiency lamps and/or ballasts $3,387 $3,222 $3,387
67,116
kWh
-
TOTAL RECOMMENDED $64,170 $45,052 $38,613
491,499
kWh
$25,557
-
MMBtu
TOTAL IMPLEMENTED $35,922 $6,452 $16,486
326,494
kWh
$19,436
-
MMBtu
Yearly Savings* Imp'd Cost* Electricity Usage Savings Natural Gas Savings
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs