Assessment Year 2025
Principal Product Concrete retaining wall and fencing components
NAICS 327390: Other Concrete Product Manufacturing
SIC 3272: Concrete Products, Except Block and Brick
Sales Range $1
M
to 5
M
# of Employees 33
Plant Area 44,028
ft2
Annual Production 40,000
ton
Production Hrs. Annual 3,510
hrs
Location (State) Colorado

Facility Energy Cost and Usage

Source Yearly Cost Usage
Electricity Usage $11,840 257,400
kWh
Electricity Demand $20,574 1,053
kW-mo/yr
Electricity Fees $2,433 -
Natural Gas $37,882 2,984
MMBtu
TOTAL YEARLY COSTS $72,729
RECOMMENDED SAVINGS* $54,509 *Non-energy impacts included in savings.
IMPLEMENTED SAVINGS* -

Recommendations

# Description Yearly Savings* Imp'd Cost* Status Electricity Usage Savings Electricity Demand Savings Natural Gas Savings LPG Savings Other Gas Savings Administrative Changes Savings
01 2.9114: Use solar heat to make electricty $12,692 $150,694 $7,534
163,803
kWh
$5,158
-
kW-mo/yr
- - - -
02 2.4226: Use / purchase optimum sized compressor $1,245 $25,405 $531
11,554
kWh
$714
-
kW-mo/yr
- - - -
03 2.4231: Reduce the pressure of compressed air to the minimum required $1,193 - $498
10,825
kWh
$695
-
kW-mo/yr
- - - -
04 2.7135: Install occupancy sensors $798 $405 $303
6,589
kWh
$495
-
kW-mo/yr
- - - -
05 2.7232: Replace existing hvac unit with high efficiency model $894 $8,570 $286
6,215
kWh
$608
-
kW-mo/yr
- - - -
06 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves $557 $217 $222
4,831
kWh
$335
-
kW-mo/yr
- - - -
07 2.4221: Install compressor air intakes in coolest locations $229 $4,085 $229
4,787
kWh
- - - - -
08 2.8226: Increase efficiency of trucks $33,068 $139,986 $(-656.8)
(-14,277)
kWh
- - $8,320
-
MMBtu
- $25,405
09 2.7491: Insulate glazing, walls, ceilings, and roofs $3,409 $4,933 - - $3,409
-
MMBtu
- - -
10 2.4322: Use or replace with energy efficient substitutes $424 $550 $(-12.1)
(-262)
kWh
- - - $436
-
MMBtu
-
TOTAL RECOMMENDED $54,509 $334,845 $8,935
194,065
kWh
$8,005
-
kW-mo/yr
$3,409
-
MMBtu
$8,320
-
MMBtu
$436
-
MMBtu
$25,405
TOTAL IMPLEMENTED - - - - - - - -
Yearly Savings* Imp'd Cost* Electricity Usage Savings Electricity Demand Savings Natural Gas Savings LPG Savings Other Gas Savings Administrative Changes Savings
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs