Assessment Year | 2023 |
---|---|
Principal Product | Custom Corrugated Cardboard Products |
NAICS | 322211: Corrugated and Solid Fiber Box Manufacturing |
SIC | 2653: Corrugated and Solid Fiber Boxes |
Sales Range | $5 M to 10M |
# of Employees | 120 |
Plant Area |
141,000
ft2
|
Annual Production | 100,000
thousand feet
|
Production Hrs. Annual | 6,250
hrs
|
Location (State) | Colorado |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $210,603 | 4,459,174 |
kWh
|
$0.047 |
Electricity Demand | $210,713 | 10,971 |
kW-mo/yr
|
$19.21 |
Electricity Fees | $63,614 | - |
|
- |
Natural Gas | $321,676 | 32,339 |
MMBtu
|
$9.95 |
TOTAL YEARLY COSTS | $806,606 | |||
RECOMMENDED SAVINGS* | $198,383 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $27,136 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Administrative Changes Savings |
---|---|---|---|---|---|---|---|---|
01 | 2.9114: Use solar heat to make electricty | $139,944 | $1,455,428 |
$124,589
2,639,603
kWh
|
$15,355
-
kW-mo/yr
|
- | - | |
02 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $17,380 | $23,925 |
$9,296
196,809
kWh
|
$8,084
-
kW-mo/yr
|
- | - | |
03 | 2.8121: Apply for tax-free status for energy purchases | $30,725 | $8,000 | - | - | - | $30,725 | |
04 | 2.1224: Replace boiler | $9,756 | $43,140 | - | - |
$9,756
-
MMBtu
|
- | |
05 | 2.2136: Install / repair insulation on steam lines | $578 | $1,310 | - | - |
$578
-
MMBtu
|
- | |
TOTAL RECOMMENDED | $198,383 | $1,531,803 |
$133,885
2,836,412
kWh
|
$23,439
-
kW-mo/yr
|
$10,334
-
MMBtu
|
$30,725 | ||
TOTAL IMPLEMENTED | $27,136 | $67,065 |
$9,296
196,809
kWh
|
$8,084
-
kW-mo/yr
|
$9,756
-
MMBtu
|
- |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs