Assessment Year | 2019 |
---|---|
Principal Product | Various Printing, Brochures, flyers, maps, etc. |
NAICS | 323111: Commercial Printing (except Screen and Books) |
SIC | 2752: Commercial Printing, Lithographic |
Sales Range | $10 M to 50M |
# of Employees | 60 |
Plant Area |
125,000
ft2
|
Annual Production | 50,000
units
|
Production Hrs. Annual | 2,500
hrs
|
Location (State) | South Carolina |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | ||
---|---|---|---|---|---|
Electricity Usage | $154,978 | 2,642,198 |
kWh
|
$0.059 | |
Electricity Demand | $62,634 | 7,425 |
kW-mo/yr
|
$8.44 | |
Electricity Fees | $1,066 | - |
|
- | |
Natural Gas | $45,660 | 59,598 |
MMBtu
|
$0.77 | |
Waste Disposal Costs | |||||
Water Usage | $2,920 | 31 |
Tgal
|
$93.51 | |
Water Disposal | $1,240 | 312 |
Tgal
|
$3.97 | |
TOTAL YEARLY COSTS | $268,498 | ||||
RECOMMENDED SAVINGS* | $11,953 |
See individual recommendations below
*Non-energy impacts included in savings.
|
|||
IMPLEMENTED SAVINGS* | $11,953 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings |
---|---|---|---|---|---|---|
01 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $7,464 | $12,357 |
$4,771
79,530
kWh
|
$2,693
-
kW-mo/yr
|
|
02 | 2.7111: Reduce illumination to minimum necessary levels | $694 | - |
$447
7,466
kWh
|
$247
-
kW-mo/yr
|
|
03 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $2,979 | $1,440 |
$1,778
29,624
kWh
|
$1,201
-
kW-mo/yr
|
|
04 | 2.7492: Use proper thickness of insulation on building envelope | $816 | $574 |
$816
13,606
kWh
|
- | |
TOTAL RECOMMENDED | $11,953 | $14,371 |
$7,812
130,226
kWh
|
$4,141
-
kW-mo/yr
|
||
TOTAL IMPLEMENTED | $11,953 | $14,371 |
$7,812
130,226
kWh
|
$4,141
-
kW-mo/yr
|
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs