Assessment Year | 2018 |
---|---|
Principal Product | Colorants and Additives |
NAICS | 325130: Synthetic Dye and Pigment Manufacturing |
SIC | 2816: Inorganic Pigments |
Sales Range | $100 M to 500M |
# of Employees | 114 |
Plant Area |
90,000
ft2
|
Annual Production | 81,954,002
lb
|
Production Hrs. Annual | 4,992
hrs
|
Location (State) | South Carolina |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | ||
---|---|---|---|---|---|
Electricity Usage | $555,152 | 11,565,675 |
kWh
|
$0.048 | |
Electricity Demand | $29,081 | 2,639 |
kW-mo/yr
|
$11.02 | |
Natural Gas | $173,465 | 32,183 |
MMBtu
|
$5.39 | |
Waste Disposal Costs | |||||
Water Usage | $234,509 | 77,900,000 |
Tgal
|
$0.003 | |
TOTAL YEARLY COSTS | $992,207 | ||||
RECOMMENDED SAVINGS* | $184,214 |
See individual recommendations below
*Non-energy impacts included in savings.
|
|||
IMPLEMENTED SAVINGS* | $41,540 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Water Usage Savings |
---|---|---|---|---|---|---|---|---|
01 | 2.1221: Replace obsolete burners with more efficient ones | $66,598 | $22,500 | - | - |
$66,598
-
MMBtu
|
- | |
02 | 2.2614: Use cooling tower or economizer to replace chiller cooling | $45,354 | $46,500 |
$31,397
654,100
kWh
|
$13,957
-
kW-mo/yr
|
- | - | |
03 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $34,631 | $52,880 |
$25,090
522,696
kWh
|
$9,541
-
kW-mo/yr
|
- | - | |
04 | 3.4156: Use flow control valves on equipment to optimize water use | $23,451 | $12,200 | - | - | - |
$23,451
-
Tgal
|
|
05 | 3.4159: Replace treated water with well / surface water | $7,271 | $4,700 | - | - | - |
$7,271
-
Tgal
|
|
06 | 2.4131: Size electric motors for peak operating efficiency | $6,909 | - |
$5,256
109,500
kWh
|
$1,653
-
kW-mo/yr
|
- | - | |
TOTAL RECOMMENDED | $184,214 | $138,780 |
$61,743
1,286,296
kWh
|
$25,151
-
kW-mo/yr
|
$66,598
-
MMBtu
|
$30,722
-
Tgal
|
||
TOTAL IMPLEMENTED | $41,540 | $52,880 |
$30,346
632,196
kWh
|
$11,194
-
kW-mo/yr
|
- | - | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Water Usage Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs