Assessment Year 2025
Principal Product Printed Materials
NAICS 323111: Commercial Printing (except Screen and Books)
SIC 2759: Commercial Printing, Not Elsewhere Classified
Sales Range $5
M
to 10
M
# of Employees 46
Plant Area 39,500
ft2
Annual Production 100,000,000
units
Production Hrs. Annual 7,488
hrs
Location (State) California

Facility Energy Cost and Usage

Source Yearly Cost Usage
Electricity Usage $182,242 1,529,641
kWh
Electricity Demand $182,829 4,587
kW-mo/yr
Electricity Fees $23,529 -
Natural Gas $41,193 3,013
MMBtu
LPG $28,080 856
MMBtu
Other Gas $4,471 1
MMBtu
Waste Disposal Costs
Water Usage $4,495 747
Tgal
Water Disposal $3,075 747
Tgal
Other Liquid (non-haz) $1,379 1
gal
TOTAL YEARLY COSTS $471,293
RECOMMENDED SAVINGS* $183,083 *Non-energy impacts included in savings.
IMPLEMENTED SAVINGS* -

Recommendations

# Description Yearly Savings* Imp'd Cost* Status Electricity Usage Savings Electricity Demand Savings LPG Savings
01 2.9114: Use solar heat to make electricty $44,753 $310,300 $28,012
235,200
kWh
$16,741
-
kW-mo/yr
-
02 2.3141: Use battery storage for demand control $38,519 $141,786 $1,951
16,384
kWh
$36,568
-
kW-mo/yr
-
03 2.2515: Use optimum thickness insulation $31,812 $49,086 $31,812
267,105
kWh
- -
04 2.8227: Adjust / maintain fork lift trucks for most efficient operation $20,329 $48,000 $(-3,389.0)
(-28,454)
kWh
$(-4,362.0)
-
kW-mo/yr
$28,080
-
MMBtu
05 2.4239: Eliminate or reduce compressed air usage $17,464 $2,000 $17,464
146,634
kWh
- -
06 2.1321: Replace fossil fuel equipment with electrical equipment $13,664 $42,200 $13,664
114,723
kWh
- -
07 2.7142: Utilize higher efficiency lamps and/or ballasts $7,568 $8,390 $2,067
17,352
kWh
$5,501
-
kW-mo/yr
-
08 2.2511: Insulate bare equipment $4,042 $6,250 $1,588
13,331
kWh
$2,454
-
kW-mo/yr
-
09 2.4133: Use most efficient type of electric motors $2,901 $860 $1,922
16,140
kWh
$979
-
kW-mo/yr
-
10 2.7135: Install occupancy sensors $2,031 $900 $1,146
9,620
kWh
$885
-
kW-mo/yr
-
TOTAL RECOMMENDED $183,083 $609,772 $96,237
808,035
kWh
$58,766
-
kW-mo/yr
$28,080
-
MMBtu
TOTAL IMPLEMENTED - - - - -
Yearly Savings* Imp'd Cost* Electricity Usage Savings Electricity Demand Savings LPG Savings
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs