ITAC Assessment: CI0043
ITAC logo
ITAC Assessment: CI0043
Grant Funding Opportunity NOW OPEN
Up to $300k at 50% cost share for qualifying* projects.
Grant Funding Opportunity Open
Qualifying* small and medium-sized US manufacturers, that received an ITAC, Onsite Energy/CHP TAP, or qualified equivalent assessment since 2018 can now apply for grants for implementation of assessment recommendations at up to 50% of qualifying* project costs with a maximum of $300,000 per grant.
IMPORTANT: The grant program now operates on a rolling basis and applications may be submitted at any time through the year, with quarterly reviews.
*See Full Grant Solicitation for full qualification and selection details.
Assessment Year 2025
Principal Product Paper Packaging and Labels
NAICS 326112: Plastics Packaging Film and Sheet (including Laminated) Manufacturing
SIC 2671: Packaging Paper and Plastics Film, Coated and Laminated
Sales Range $10
M
to 50
M
# of Employees 79
Plant Area 62,000
ft2
Annual Production 50,000,000
units
Production Hrs. Annual 4,524
hrs
Location (State) California

Facility Energy Cost and Usage

Source Yearly Cost Usage
Electricity Usage $184,806 1,103,240
kWh
Electricity Demand $96,567 15,685
kW-mo/yr
Electricity Fees $36,353 -
Natural Gas $695 27
MMBtu
Waste Disposal Costs
Water Usage $4,175 465
Tgal
Water Disposal $2,519 465
Tgal
TOTAL YEARLY COSTS $325,115
RECOMMENDED SAVINGS* $212,342 *Non-energy impacts included in savings.
IMPLEMENTED SAVINGS* -

Recommendations

# Description Yearly Savings* Imp'd Cost* Status Electricity Usage Savings Electricity Demand Savings Increase in Production Savings
01 2.4323: Use optimum size and capacity equipment $143,742 $300,000 $1,242
7,415
kWh
- $142,500
02 2.7142: Utilize higher efficiency lamps and/or ballasts $18,970 $7,350 $16,683
99,600
kWh
$2,287
-
kW-mo/yr
-
03 2.7135: Install occupancy sensors $18,838 $12,100 $17,031
101,679
kWh
$1,807
-
kW-mo/yr
-
04 2.4146: Use adjustable frequency drive or multiple speed motors on existing system $14,483 $12,000 $13,196
78,784
kWh
$1,287
-
kW-mo/yr
-
05 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves $8,106 $23,794 $6,871
41,019
kWh
$1,235
-
kW-mo/yr
-
06 2.4133: Use most efficient type of electric motors $3,043 $1,380 $2,836
16,928
kWh
$207
-
kW-mo/yr
-
07 2.7134: Use photocell controls $2,912 $8,100 $2,529
15,096
kWh
$383
-
kW-mo/yr
-
08 2.3132: Recharge batteries on during off-peak demand periods $2,248 $800 - $2,248
-
kW-mo/yr
-
TOTAL RECOMMENDED $212,342 $365,524 $60,388
360,521
kWh
$9,454
-
kW-mo/yr
$142,500
TOTAL IMPLEMENTED - - - - -
Yearly Savings* Imp'd Cost* Electricity Usage Savings Electricity Demand Savings Increase in Production Savings
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs