ITAC Assessment: CI0022
ITAC logo
ITAC Assessment: CI0022
Grant Funding Opportunity NOW OPEN
Up to $300k at 50% cost share for qualifying* projects.
Grant Funding Opportunity Open
Qualifying* small and medium-sized US manufacturers, that received an ITAC, Onsite Energy/CHP TAP, or qualified equivalent assessment since 2018 can now apply for grants for implementation of assessment recommendations at up to 50% of qualifying* project costs with a maximum of $300,000 per grant.
IMPORTANT: The grant program now operates on a rolling basis and applications may be submitted at any time through the year, with quarterly reviews.
*See Full Grant Solicitation for full qualification and selection details.
Assessment Year 2023
Principal Product Soy Products
NAICS 311991: Perishable Prepared Food Manufacturing
SIC 2099: Food Preparations, Not Elsewhere Classified
Sales Range $10
M
to 50
M
# of Employees 45
Plant Area 25,000
ft2
Annual Production 3,000,000
lb
Production Hrs. Annual 6,240
hrs
Location (State) California

Facility Energy Cost and Usage

Source Yearly Cost Usage
Electricity Usage $64,753 419,136
kWh
Electricity Demand $27,962 1,768
kW-mo/yr
Electricity Fees $12,920 -
Natural Gas $36,451 2,161
MMBtu
LPG $22,550 2,000
MMBtu
Waste Disposal Costs
Water Usage $30,110 3,890
Tgal
Water Disposal $680 3,890
Tgal
TOTAL YEARLY COSTS $195,426
RECOMMENDED SAVINGS* $101,280 *Non-energy impacts included in savings.
IMPLEMENTED SAVINGS* -

Recommendations

# Description Yearly Savings* Imp'd Cost* Status Electricity Usage Savings Electricity Demand Savings LPG Savings
01 2.9114: Use solar heat to make electricty $30,795 $185,422 $26,697
172,800
kWh
$4,098
-
kW-mo/yr
-
02 2.1321: Replace fossil fuel equipment with electrical equipment $18,385 $60,000 $(-4,165.0)
(-26,957)
kWh
- $22,550
-
MMBtu
03 2.2442: Preheat combustion air with waste heat $17,839 $9,000 $14,408
93,255
kWh
$3,431
-
kW-mo/yr
-
04 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves $12,948 $300 $11,788
76,296
kWh
$1,160
-
kW-mo/yr
-
05 2.4239: Eliminate or reduce compressed air usage $10,784 - $10,784
69,798
kWh
- -
06 2.3132: Recharge batteries on during off-peak demand periods $5,312 $50 - $5,312
-
kW-mo/yr
-
07 2.7142: Utilize higher efficiency lamps and/or ballasts $3,547 $7,400 $2,545
16,472
kWh
$1,002
-
kW-mo/yr
-
08 2.7135: Install occupancy sensors $1,670 $1,125 $1,370
8,869
kWh
$300
-
kW-mo/yr
-
TOTAL RECOMMENDED $101,280 $263,297 $63,427
410,533
kWh
$15,303
-
kW-mo/yr
$22,550
-
MMBtu
TOTAL IMPLEMENTED - - - - -
Yearly Savings* Imp'd Cost* Electricity Usage Savings Electricity Demand Savings LPG Savings
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs