ITAC Assessment: CI0003
ITAC logo
ITAC Assessment: CI0003
Grant Funding Opportunity NOW OPEN
Up to $300k at 50% cost share for qualifying* projects.
Grant Funding Opportunity Open
Qualifying* small and medium-sized US manufacturers, that received an ITAC, Onsite Energy/CHP TAP, or qualified equivalent assessment since 2018 can now apply for grants for implementation of assessment recommendations at up to 50% of qualifying* project costs with a maximum of $300,000 per grant.
IMPORTANT: The grant program now operates on a rolling basis and applications may be submitted at any time through the year, with quarterly reviews.
*See Full Grant Solicitation for full qualification and selection details.
Assessment Year 2022
Principal Product Beer/Alcohol
NAICS 488991: Packing and Crating
SIC 5181: Beer and Ale
Sales Range $100
M
to 500
M
# of Employees 250
Plant Area 573,698
ft2
Annual Production 10,000,000
pieces
Production Hrs. Annual 7,488
hrs
Location (State) California

Facility Energy Cost and Usage

Source Yearly Cost Usage
Electricity Usage $325,268 1,905,600
kWh
Electricity Demand $35,907 14,368
kW-mo/yr
Electricity Fees $45,631 -
Natural Gas $2,372 152
MMBtu
Waste Disposal Costs
Water Usage $1,456 155
Tgal
Solid Waste (non-haz) $1,122 155
lb
TOTAL YEARLY COSTS $411,756
RECOMMENDED SAVINGS* $154,739 *Non-energy impacts included in savings.
IMPLEMENTED SAVINGS* -

Recommendations

# Description Yearly Savings* Imp'd Cost* Status Electricity Usage Savings Electricity Demand Savings
01 2.7491: Insulate glazing, walls, ceilings, and roofs $87,136 $114,800 $87,136
510,496
kWh
-
02 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves $30,546 $600 $29,177
170,933
kWh
$1,369
-
kW-mo/yr
03 2.9114: Use solar heat to make electricty $16,393 $82,655 $15,007
87,919
kWh
$1,386
-
kW-mo/yr
04 2.4133: Use most efficient type of electric motors $7,448 $7,600 $7,114
41,678
kWh
$334
-
kW-mo/yr
05 2.4146: Use adjustable frequency drive or multiple speed motors on existing system $6,715 $8,580 $6,689
39,187
kWh
$26
-
kW-mo/yr
06 2.7134: Use photocell controls $3,744 $1,166 $3,658
21,431
kWh
$86
-
kW-mo/yr
07 2.4231: Reduce the pressure of compressed air to the minimum required $1,557 $25 $1,487
8,711
kWh
$70
-
kW-mo/yr
08 2.3132: Recharge batteries on during off-peak demand periods $1,200 $500 - $1,200
-
kW-mo/yr
TOTAL RECOMMENDED $154,739 $215,926 $150,268
880,355
kWh
$4,471
-
kW-mo/yr
TOTAL IMPLEMENTED - - - -
Yearly Savings* Imp'd Cost* Electricity Usage Savings Electricity Demand Savings
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs