Assessment Year | 2024 |
---|---|
Principal Product | Olechemicals |
NAICS | 325199: All Other Basic Organic Chemical Manufacturing |
SIC | 2869: Industrial Organic Chemicals, Not Elsewhere Classified |
Sales Range | $10 M to 50M |
# of Employees | 35 |
Plant Area |
42,000
ft2
|
Annual Production | 30,000,000
lb
|
Production Hrs. Annual | 6,240
hrs
|
Location (State) | North Carolina |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $71,386 | 1,282,166 |
kWh
|
$0.056 |
Electricity Demand | $54,844 | 3,242 |
kW-mo/yr
|
$16.92 |
Electricity Fees | $1,402 | - |
|
- |
Natural Gas | $203,626 | 48,922 |
MMBtu
|
$4.16 |
TOTAL YEARLY COSTS | $331,258 | |||
RECOMMENDED SAVINGS* | $84,124 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | - |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings |
---|---|---|---|---|---|---|---|
01 | 2.4146: Use adjustable frequency drive or multiple speed motors on existing system | $10,082 | $7,780 |
$6,359
113,552
kWh
|
$3,723
-
kW-mo/yr
|
- | |
02 | 2.6218: Turn off equipment when not in use | $8,467 | - |
$8,467
151,191
kWh
|
- | - | |
03 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $718 | $1,000 |
$454
8,112
kWh
|
$264
-
kW-mo/yr
|
- | |
04 | 2.4146: Use adjustable frequency drive or multiple speed motors on existing system | $4,557 | $5,600 |
$2,628
46,930
kWh
|
$1,929
-
kW-mo/yr
|
- | |
05 | 2.2437: Recover waste heat from equipment | $21,466 | $68,475 |
$3,569
63,724
kWh
|
- |
$17,897
-
MMBtu
|
|
06 | 2.2162: Reduce excess steam bleeding | $11,803 | - | - | - |
$11,803
-
MMBtu
|
|
07 | 2.6221: Use most efficient equipment at it's maximum capacity and less efficient equipment only when necessary | $2,905 | - | - | - |
$2,905
-
MMBtu
|
|
08 | 2.4111: Utilize energy-efficient belts and other improved mechanisms | $878 | $2,642 |
$435
7,764
kWh
|
$443
-
kW-mo/yr
|
- | |
09 | 2.9114: Use solar heat to make electricty | $23,248 | $226,305 |
$23,248
415,134
kWh
|
- | - | |
TOTAL RECOMMENDED | $84,124 | $311,802 |
$45,160
806,407
kWh
|
$6,359
-
kW-mo/yr
|
$32,605
-
MMBtu
|
||
TOTAL IMPLEMENTED | - | - | - | - | - | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings |