Assessment Year | 2005 |
---|---|
Principal Product | Corrugated Boxes |
NAICS | 322211: Corrugated and Solid Fiber Box Manufacturing |
SIC | 2653: Corrugated and Solid Fiber Boxes |
Sales Range | $50 M to 100M |
# of Employees | 200 |
Plant Area |
137,500
ft2
|
Annual Production | 336,759
thousand feet
|
Production Hrs. Annual | 6,864
hrs
|
Location (State) | Georgia |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $231,548 | 6,107,115 |
kWh
|
$0.038 |
Electricity Demand | $121,468 | 13,388 |
kW-mo/yr
|
$9.07 |
Electricity Fees | $26,571 | - |
|
- |
Natural Gas | $510,783 | 65,949 |
MMBtu
|
$7.75 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $84,557 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $27,997 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Administrative Changes Savings |
---|---|---|---|---|---|---|---|---|
01 | 2.2121: Increase amount of condensate returned | $15,818 | $4,500 | - | - |
$15,818
-
MMBtu
|
- | |
02 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $7,467 | $7,195 |
$5,103
135
kWh
|
$2,364
-
kW-mo/yr
|
- | - | |
03 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $2,196 | $1,422 |
$1,426
37,890
kWh
|
$770
-
kW-mo/yr
|
- | - | |
04 | 2.4111: Utilize energy-efficient belts and other improved mechanisms | $7,351 | $5,122 |
$4,767
126,785
kWh
|
$2,584
-
kW-mo/yr
|
- | - | |
05 | 2.7316: Centralize control of exhaust fans to ensure their shutdown, or establish program to ensure manual shutdown | $31,493 | $25,500 | - | - |
$31,493
-
MMBtu
|
- | |
06 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $2,632 | $800 |
$1,825
48,527
kWh
|
$807
-
kW-mo/yr
|
- | - | |
07 | 2.4146: Use adjustable frequency drive or multiple speed motors on existing system | $9,858 | $30,000 |
$3,604
95,857
kWh
|
$6,254
-
kW-mo/yr
|
- | - | |
08 | 2.8112: Combine utility meters | $7,742 | $2,000 | - | - | - | $7,742 | |
TOTAL RECOMMENDED | $84,557 | $76,539 |
$16,725
309,194
kWh
|
$12,779
-
kW-mo/yr
|
$47,311
-
MMBtu
|
$7,742 | ||
TOTAL IMPLEMENTED | $27,997 | $11,844 |
$8,018
213,202
kWh
|
$4,161
-
kW-mo/yr
|
$15,818
-
MMBtu
|
- | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Administrative Changes Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs