| Assessment Year | 2024 |
|---|---|
| Principal Product | Water Activated Tape |
| NAICS | 322220: Paper Bag and Coated and Treated Paper Manufacturing |
| SIC | 2672: Coated and Laminated Paper, Not Elsewhere Classified |
| Sales Range | $100 M to 500M |
| # of Employees | 84 |
| Plant Area |
129,000
ft2
|
| Annual Production | 240,000,000
units
|
| Production Hrs. Annual | 8,760
hrs
|
| Location (State) | North Carolina |
Facility Energy Cost and Usage
| Source | Yearly Cost | Usage | Unit Cost | |
|---|---|---|---|---|
| Electricity Usage | $385,031 | 6,565,215 |
kWh
|
$0.059 |
| Electricity Demand | $135,768 | 11,258 |
kW-mo/yr
|
$12.06 |
| Natural Gas | $436,745 | 57,867 |
MMBtu
|
$7.55 |
| TOTAL YEARLY COSTS | $957,544 | |||
| RECOMMENDED SAVINGS* | $217,168 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
| IMPLEMENTED SAVINGS* | - | |||
Recommendations
| # | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings |
|---|---|---|---|---|---|---|---|
| 01 | 2.2449: Recover heat from exhausted steam, hot air or hot water | $156,555 | $230,000 | - | - |
$156,555
-
MMBtu
|
|
| 02 | 2.4322: Use or replace with energy efficient substitutes | $4,410 | $15,880 |
$2,514
42,048
kWh
|
$1,896
-
kW-mo/yr
|
- | |
| 03 | 2.4231: Reduce the pressure of compressed air to the minimum required | $3,026 | - |
$2,371
39,645
kWh
|
$655
-
kW-mo/yr
|
- | |
| 04 | 2.2136: Install / repair insulation on steam lines | $3,017 | $3,056 | - | - |
$3,017
-
MMBtu
|
|
| 05 | 2.9114: Use solar heat to make electricty | $50,160 | $549,139 |
$50,160
850,169
kWh
|
- | - | |
| TOTAL RECOMMENDED | $217,168 | $798,075 |
$55,045
931,862
kWh
|
$2,551
-
kW-mo/yr
|
$159,572
-
MMBtu
|
||
| TOTAL IMPLEMENTED | - | - | - | - | - | ||
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs