Assessment Year | 2019 |
---|---|
Principal Product | Storage |
NAICS | 424490: Other Grocery and Related Products Merchant Wholesalers |
SIC | 5149: Groceries and Related Products, Not Elsewhere Classified |
Sales Range | greater than $500 M |
# of Employees | 200 |
Plant Area |
685,000
ft2
|
Annual Production | 29,000,000
pieces
|
Production Hrs. Annual | 7,452
hrs
|
Location (State) | Washington |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | ||
---|---|---|---|---|---|
Electricity Usage | $294,642 | 4,228,180 |
kWh
|
$0.070 | |
Electricity Demand | $79,167 | 9,590 |
kW-mo/yr
|
$8.26 | |
Natural Gas | $90,000 | 172,275 |
MMBtu
|
$0.52 | |
Waste Disposal Costs | |||||
Water Usage | $13,000 | 13,500 |
Tgal
|
$0.96 | |
TOTAL YEARLY COSTS | $476,809 | ||||
RECOMMENDED SAVINGS* | $19,413 |
See individual recommendations below
*Non-energy impacts included in savings.
|
|||
IMPLEMENTED SAVINGS* | - |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings |
---|---|---|---|---|---|---|
01 | 2.4111: Utilize energy-efficient belts and other improved mechanisms | $308 | $53 |
$257
3,666
kWh
|
$51
-
kW-mo/yr
|
|
02 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $2,569 | $1,440 |
$2,011
28,741
kWh
|
$558
-
kW-mo/yr
|
|
03 | 2.4231: Reduce the pressure of compressed air to the minimum required | $130 | $20 |
$77
1,094
kWh
|
$53
-
kW-mo/yr
|
|
04 | 2.2621: Modify refrigeration system to operate at a lower pressure | $16,406 | $13,000 |
$16,406
234,368
kWh
|
- | |
TOTAL RECOMMENDED | $19,413 | $14,513 |
$18,750
267,870
kWh
|
$663
-
kW-mo/yr
|
||
TOTAL IMPLEMENTED | - | - | - | - |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs