| Assessment Year | 2010 |
|---|---|
| Principal Product | Mechanical seals and sealing systems |
| NAICS | 339991: Gasket, Packing, and Sealing Device Manufacturing |
| SIC | 3053: Gaskets, Packing, and Sealing Devices |
| Sales Range | $10 M to 50M |
| # of Employees | 68 |
| Plant Area |
8,275
ft2
|
| Annual Production | 141,600
pieces
|
| Production Hrs. Annual | 5,516
hrs
|
| Location (State) | Texas |
Facility Energy Cost and Usage
| Source | Yearly Cost | Usage | Unit Cost | |
|---|---|---|---|---|
| Electricity Usage | $64,638 | 701,280 |
kWh
|
$0.092 |
| Electricity Demand | $10,994 | 2,279 |
kW-mo/yr
|
$4.82 |
| TOTAL YEARLY COSTS | - | |||
| RECOMMENDED SAVINGS* | $39,772 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
| IMPLEMENTED SAVINGS* | $31,757 | |||
Recommendations
| # | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Personnel Changes Savings | Administrative Changes Savings | One-time Revenue or Avoided Cost Savings |
|---|---|---|---|---|---|---|---|---|---|
| 01 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $5,635 | $11,600 |
$4,980
52,400
kWh
|
$655
-
kW-mo/yr
|
- | - | - | |
| 02 | 2.8121: Apply for tax-free status for energy purchases | $26,812 | $2,680 | - | - | - | $5,362 | $21,450 | |
| 03 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $2,000 | $500 |
$1,770
18,600
kWh
|
$230
-
kW-mo/yr
|
- | - | - | |
| 04 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $1,755 | $460 |
$280
2,940
kWh
|
$20
-
kW-mo/yr
|
$1,455 | - | - | |
| 05 | 2.3212: Optimize plant power factor | $1,670 | $5,830 | - |
$1,670
-
kW-mo/yr
|
- | - | - | |
| 06 | 2.4231: Reduce the pressure of compressed air to the minimum required | $1,190 | - |
$1,050
11,060
kWh
|
$140
-
kW-mo/yr
|
- | - | - | |
| 07 | 2.7124: Make a practice of turning off lights when not needed | $710 | $500 |
$710
7,500
kWh
|
- | - | - | - | |
| TOTAL RECOMMENDED | $39,772 | $21,570 |
$8,790
92,500
kWh
|
$2,715
-
kW-mo/yr
|
$1,455 | $5,362 | $21,450 | ||
| TOTAL IMPLEMENTED | $31,757 | $3,640 |
$3,100
32,600
kWh
|
$390
-
kW-mo/yr
|
$1,455 | $5,362 | $21,450 | ||
| Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Personnel Changes Savings | Administrative Changes Savings | One-time Revenue or Avoided Cost Savings | |||
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs