Assessment Year | 2014 |
---|---|
Principal Product | Seafood |
NAICS | 311710: Seafood Product Preparation and Packaging |
SIC | 2092: Prepared Fresh or Frozen Fish and Seafoods |
Sales Range | $10 M to 50M |
# of Employees | 189 |
Plant Area |
35,000
ft2
|
Annual Production | 55,000,000
lb
|
Production Hrs. Annual | 6,480
hrs
|
Location (State) | Alaska |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $1,000,310 | 6,965,760 |
kWh
|
$0.14 |
Electricity Demand | $116,263 | 20,505 |
kW-mo/yr
|
$5.67 |
Fuel Oil #2 | $259,082 | 14,076 |
MMBtu
|
$18.41 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $237,407 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $60,446 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Fuel Oil #2 Savings | Water Disposal Savings | Personnel Changes Savings | Administrative Changes Savings |
---|---|---|---|---|---|---|---|---|---|---|
01 | 2.6218: Turn off equipment when not in use | $170,064 | $46,000 | - | - |
$170,064
-
MMBtu
|
- | - | - | |
02 | 3.4154: Eliminate leaks in water lines and valves | $2,822 | $2,600 | - | - | - |
$3,272
-
Tgal
|
$(-450.0) | - | |
03 | 2.2511: Insulate bare equipment | $338 | $893 | - | - |
$338
-
MMBtu
|
- | - | - | |
04 | 2.2621: Modify refrigeration system to operate at a lower pressure | $26,828 | $9,000 |
$25,307
176,234
kWh
|
$1,521
-
kW-mo/yr
|
- | - | - | - | |
05 | 2.2515: Use optimum thickness insulation | $9,004 | $6,600 |
$9,004
62,703
kWh
|
- | - | - | - | - | |
06 | 2.4111: Utilize energy-efficient belts and other improved mechanisms | $12,633 | $872 |
$11,180
77,853
kWh
|
$1,453
-
kW-mo/yr
|
- | - | - | - | |
07 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $4,856 | $10,866 |
$4,265
29,701
kWh
|
$591
-
kW-mo/yr
|
- | - | - | - | |
08 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $3,695 | $10,868 |
$3,443
23,976
kWh
|
$252
-
kW-mo/yr
|
- | - | - | - | |
09 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $5,126 | $1,190 |
$4,963
34,560
kWh
|
$163
-
kW-mo/yr
|
- | - | - | - | |
10 | 2.7135: Install occupancy sensors | $2,041 | $610 |
$1,993
13,877
kWh
|
- | - | - | - | $48 | |
TOTAL RECOMMENDED | $237,407 | $89,499 |
$60,155
418,904
kWh
|
$3,980
-
kW-mo/yr
|
$170,402
-
MMBtu
|
$3,272
-
Tgal
|
$(-450.0) | $48 | ||
TOTAL IMPLEMENTED | $60,446 | $32,023 |
$53,897
375,326
kWh
|
$3,389
-
kW-mo/yr
|
$338
-
MMBtu
|
$3,272
-
Tgal
|
$(-450.0) | - | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Fuel Oil #2 Savings | Water Disposal Savings | Personnel Changes Savings | Administrative Changes Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs